Eaton Electrical Series NRX User Manual
Page 3
Effective 10/08
For more information visit: www.eaton.com/seriesnrx
3
IL01301016E
Universal Bus Adapter
Proceed with the following 3 steps:
Step 1: Bolt a universal bus adapter
to the vertically positioned mounting
holes of a primary terminal pad for a
horizontal bus connection or to the
horizontally positioned mounting
holes for a vertical bus connection as
shown using the hardware provided.
Torque the bolted connection to 120
in-lbs (13.6 N-m) using a torque
wrench.
Step 2: Complete all six adapter
connections (eight for 4-pole) in a
similar fashion. The line and load
adapters can be mounted in opposite
directions as shown.
Step 3: Reverse the procedure just
described to remove the adapters.
Cable Adapter
Proceed with the following 4 steps:
Step 1: A cable adapter can be bolt-
ed directly to the straight bus
adapter using the hardware provided
as shown. Torque the bolted con-
nection to 240 in-lbs (27 N-m) using
a torque wrench.
.
Step 2: Complete all six cable
adapter connections (eight for 4-
pole) in a similar fashion. Make cer-
tain that the adapters are mounted
pointing in the proper direction as
shown.
Step 3: Reverse the procedure just
described to remove the adapters.
Step 4: When making the actual
cable connections, properly torque
Step 1
Step 2
Step 1
Step 2
6
For more information visit: www.eaton.com/seriesnrx
Effective 10/08
IL01301016E