Type tests and environmental conditions – Westermo MDW-45 User Manual
Page 10

10
6617-2203
Type tests and environmental conditions
Electromagnetic Compatibility
Phenomena
Test
Description
Level
ESD
EN 61000-4-2
Enclosure contact
± 6 kV
Enclosure air
± 8 kV
RF field AM modulated
IEC 61000-4-3
Enclosure
10 V/m 80% AM (1 kHz), 80 – 1 000 MHz
20 V/m 80% AM (1 kHz), 800 – 960 MHz
20 V/m 80% AM (1 kHz), 1 400 – 2 700 MHz
RF field 900 MHz
ENV 50204
Enclosure
20 V/m pulse modulated 200 Hz, 900 ± 5 MHz
Fast transient
EN 61000-4-4
Signal ports
± 2 kV
Power ports
± 2 kV
Surge
EN 61000-4-5
Signal ports unbalanced ± 2 kV line to earth, ± 2 kV line to line
Signal ports balanced
± 2 kV line to earth, ± 1 kV line to line
Power ports
± 2 kV line to earth, ± 2 kV line to line
RF conducted
EN 61000-4-6
Signal ports
10 V 80% AM (1 kHz), 0.15 – 80 MHz
Power ports
10 V 80% AM (1 kHz), 0.15 – 80 MHz
Magnetic field, power freq.
EN 61000-4-8
Enclosure
100 A/m, 50 Hz, 16.7 Hz & 0 Hz
Pulse Magnetic field
EN 61000-4-9
Enclosure
300 A/m, 6.4 / 16 ms pulse
Voltage dips and interruption EN 61000-4-11
AC power ports
10, 20 & 5000 ms, interruptions
10 & 500 ms, 30% reduction
100, 200 & 1 000 ms, 60% reduction
Mains freq. 50 Hz
EN 61000-4-16
Signal ports
100 V 50 Hz
Mains freq. 50 Hz
SS 436 15 03
Signal ports
250 V 50 Hz
Voltage dips and interruption
EN 61000-4-29
DC power ports
10 & 100 ms, interruption
10 ms, 30% reduction
10 ms, 60% reduction
+20% above & –20% below rated voltage
Radiated emission
EN 55022
Enclosure
Class B
FCC part 15
Class B
Conducted emission
EN 55022
AC power ports
Class B
FCC part 15
AC power ports
Class B
EN 55022
DC power ports
Class B
Dielectric strength
Signal port to all other
2 kVrms 50 Hz 1min
Power port to all other 3 kVrms 50 Hz 1min
2 kVrms 50 Hz 1min (@ rated power < 60V)
MDW-45 LV EX Any port to any port
and enclosure
0,5 kVrms 50 Hz 1 min
Environmental
Temperature
Operating
–40 to +70°C
Storage & Transport
–40 to +70°C
Humidity
Operating
5 to 95% relative humidity
Storage & Transport
5 to 95% relative humidity
Altitude
Operating
2 000 m / 70 kPa
Service life
Operating
10 year
Vibration
IEC 60068-2-6
Operating
7.5 mm, 5 – 8 Hz
2 g, 8 – 500 Hz
Shock
IEC 60068-2-27 Operating
15 g, 11 ms
Packaging
Enclosure, MDW-45
UL 94
PC / ABS
Flammability class V-1
Enclosure, MDW-45 EX
Cabelec 6141
Dimension W x H x D
35 x 121 x 119 mm
Weight
0.19 kg
Degree of protection
IEC 529
Enclosure
IP 21
Cooling
Convection
Mounting
Horizontal on 35 mm DIN-rail