RS-422/485 was designed for multidrop applications. When a system is installed it should
form a bus structure (see diagrams). Star shaped networks should never be created,
there are other Westermo products designed to work in star net applications. To get a
correct installation according to the RS-422/485 specification it´s very important that the
line is terminated at the correct points. The recommendation is to terminate the recei-
ver on the master unit and the final bus slave unit. See diagrams for details of how this is
done with RS-485 (2-wire) and RS-422 (4-wire).

The line transmitter used in the MD-44 is activated by data received on the RS-232
interface, unlike conventional converters that rely on a control signal (e.g. RTS).

If any problems do occur on set up of the MD-44, the LED’s will be helpful.

• PWR:

The unit has power.

• RD:

Data received on the RS-422/485 interface.

• DCD:

Follows RD in two wire operation. Always active for four wire.

• CTS:

Follows RTS.

• RTS:

Status of RTS from the RS-232 interface.

• TD:

Data received on RS-232 interface.

=Termination

Max 32 connections

Max 1 200 metres

Max 0.3 metre

=Termination

Max 32 connections

A
B

A

B

A

B

A

B

A’
B’
A
B

B’ A’

A’

B

B

A

B’ A’ B A

A

B’

N.B. R+/R–, T+/T– definitations are not standard, it can help to shift A and B

if the unit does not work.