beautypg.com

Westermo FD-10 User Manual

Page 22

background image

22

6630-2212

7.2 Addressed, serial transfer master, FD-10 A

Transfer defined PROFIBUS I/O data modules between two FD-10’s, each time on
demand by a PROFIBUS DP master. FD-10 A is the serial transfer master that transfer
I/O data between various FD-10’s, selected by serial transfer address.This serial address-
ing enable access to up to 255 independent remote PROFIBUS DP nets by only one
serial transmission line (e.g. radio system or RS-485).

By FD-Tool defined PROFIBUS I/O modules will be mirrored between FD-10 A and the
serial addressed FD-10 P at the other side. Input modules of FD-10 will be sent to out-
put modules of FD-10 at the other side, and vice versa. Note that one data word com-
mand output and one data word status input has to be included in PROFIBUS I/O data
of FD-10 A.The command control the serial transfer and the status return information
about the transfer.

FD-10 can transfer frames when the unit is in normal operation mode and the
PROFIBUS DP is active, LED CONF inactive and BA active.

7.2.1 Basic configuration

Serial transfer > Serial interface

Select the desired parameters of the Serial interface.

PROFIBUS-DP > PROFIBUS DP parameters

PROFIBUS DP Address

Set this FD-10 PROFIBUS DP address.

Number of I/O Modules

Set the number of I/O modules used by this FD-10.
Module 1 and up to selected “Number of I/O Modules”
will be used by FD-10.

I/O module 1–4 > I/O module 1

Data type

Select data type for I/O module 1.

Module type

Select module type for I/O module 1.

Data length

Set data length of I/O module 1. Note that data length is
related to selected data type, byte or word. Byte has a
length of 8 bit and word 16 bits.

Identifier [hex]

Show the resulting identifier in hex.

The same content for all I/O modules, 1 to 8. Module 1 and up to selected
“Number of I/O Modules” will be used by FD-10.