Verilink 1200 Rack Pwr Spply (IG) Configuration/Installation Guide User Manual
1200 rmps, Rack mount power supply), Specifications

T
R
A
N
S
P
O
R
T
®
1200 RMPS
(Rack Mount Power Supply)
Part Number 45- 00032
Rev 2.0
T
R
A
N
S
P
O
R
T
®
The TxPORT 1200 RMPS installs in a standard 19" rack. When inserting the unit, install the bottom two screws in the mounting brackets first.
This will prevent the weight of the unit from potentially bending the mounting brackets. The 1200 RMPS weighs up to 60 pounds. Use
extreme caution when installing the unit in the rack to avoid possible personal injury and/or damage to other equipment.
AC power is acquired through an industry standard 110 V power cord (supplied).
The alarm contacts on the ALARM barrier strip (rear panel) are labeled COM (common), NC (normally closed), and NO (normally open). The
alarm may be cut off with the ALARM CUT OFF switch (front panel).
The 1200 contains no user-serviceable parts or field options. If servicing or power optioning (24/48 VDC) is required, return the unit t o
T x P O RT C u s t o m e r S e r v i c e .
Fused Outputs:
16 individual fused outputs (3 amps, GMT type)
Overload Protection: Current limited, constant voltage transformer
Input Fuse:
6.3 amps
Input Connectors:
Industry standard AC male connector
Output Connectors:
Screw terminal, 16 position
LED Indicators:
Power ON/OFF, Fuse Alarm, Alarm Cut-off
Isolation Rating:
Class 130, UL 1446
POWER
Current:
48 VDC, 5 amps redundant or 10 amps non-redundant
24 VDC, 10 amps redundant or 20 amps non-redundant
AC Input:
100 -130 VAC, 60 Hz, 6 amps (maximum)
Power Input:
300 watts (maximum)
Heat Generation:
204 BTU
Efficiency:
80%
MECHANICAL
Dimensions:
16" W, 5" H, 12" D
Weight:
60 lbs. (maximum)
Cooling:
Forced air
ENVIRONMENTAL
Operating Temp:
0° to 60° C (32° to 140°F)
Storage Temp:
-20° to 80° C (- 4° to 176°F)
Humidity:
95% maximum, non - condensing
NEBS Zone 4:
Certified
-48 VDC
9 10111213141516
-48 VDC
1 2 3 4 5 6 7 8
RTN
1 2 3 4 5 6 7 8
RTN
9 10111213141516
ALARM
COM NC NO
MODEL NO.
SERIAL NO.
I
O
FUSE
Rear Panel
Front Panel
SPECIFICATIONS
1200 RMPS
ALARM
ALARM
CUT OFF
POWER
1
Fused Output
2 3 4 5 6 7 8
9 10111213141516
Fused Output