Technical data, Customer service and guarantee – REMKO PWW 6000 User Manual
Page 9

9
Technical Data
1) Measurement at intervals of 5 m, measuring room volume 800 m³, average reverberation time 1.4 s
Type
BG 30 - 2
BG 30 - 3
BG 30 - 4
BG 50 - 2
BG 50 - 3
BG 50 - 4
Electrical connection
V
400/3N~
400/3N~
400/3N~
400/3N~
400/3N~
400/3N~
Frequency
Hz
50
50
50
50
50
50
Power consumption
kW
0.13/0.10
0.13/0.10
0.13/0.10
0.26/0.18
0.26/0.18
0.26/0.18
Rated current
A
0.26/0.16
0.26/0.16
0.26/0.16
0.52/0.29
0.52/0.29
0.52/0.29
Speed
U/min 1340/1040 1340/1040 1340/1040 1360/1020 1360/1020 1360/1020
Air capacity
m³/h 2250/1850 2050/1640 1850/1500 3800/3180 3400/2870 3150/2770
Sound pressure level
1)
dB(A)
52/46
53/48
55/49
55/50
55/51
58/54
Heating medium connection inch
R¾"
R1"
R1¼"
R¾"
R1"
R1¼"
Heating medium
Pump warm water or pump hot water up to max. 130 °C
Operating pressure
bar
16
16
16
16
16
16
Weight
kg
24
26
27
31
34
36
Type
BG 80 - 2
BG 80 - 3
BG 80 - 4 BG 100 - 2 BG 100 - 3 BG 100 - 4
Electrical connection
V
400/3N~
400/3N~
400/3N~
400/3N~
400/3N~
400/3N~
Frequency
Hz
50
50
50
50
50
50
Power consumption
kW
0.42/0.28
0.42/0.28
0.42/0.28
0.76/0.47
0.76/0.47
0.76/0.47
Rated current
A
0.76/0.46
0.76/0.46
0.76/0.46
1.50/0.81
1.50/0.81
1.50/0.81
Speed
U/min
880/670
880/670
880/670
870/650
870/650
870/650
Air capacity
m³/h 5800/4400 5400/4300 4730/3700 9050/7400 8250/6620 7670/6180
Sound pressure level
1)
dB(A)
55/49
55/49
55/49
58/54
58/54
59/55
Heating medium connection inch
R1"
R1¼"
R1¼"
R1¼"
R1½"
R1½"
Heating medium
Pump warm water or pump hot water up to max. 130 °C
Operating pressure
bar
16
16
16
16
16
16
Weight
kg
44
47
51
58
60
68
Proper use
The units are designed exclusively for industrial and com-
mercial heating and insulation purposes on the basis of
their design and equipment.
The manufacturer assumes no liability for damage re-
sulting from non-compliance with manufacturer specifi-
cations and legal requirements, or if modifications are
made to the units.
*
Operation/handling which does not comply with
these instructions is prohibited!
In cases of non-compliance, we assume no liability
and the guarantee becomes null and void.
Customer Service and
Guarantee
For the guarantee to be valid, the purchaser or his cus-
tomer must completely fill out the "guarantee certificate"
enclosed with all units and send it back to REMKO GmbH
& Co. KG
.
The units are repeatedly tested at the production site to
ensure that they are working properly. If a malfunction
occurs that cannot be eliminated by the operating per-
sonnel, please contact your dealer or contract partner.