Technical Data

1) Measurement at intervals of 5 m, measuring room volume 800 m³, average reverberation time 1.4 s

Type

BG 30 - 2

BG 30 - 3

BG 30 - 4

BG 50 - 2

BG 50 - 3

BG 50 - 4

Electrical connection

V

400/3N~

400/3N~

400/3N~

400/3N~

400/3N~

400/3N~

Frequency

Hz

50

50

50

50

50

50

Power consumption

kW

0.13/0.10

0.13/0.10

0.13/0.10

0.26/0.18

0.26/0.18

0.26/0.18

Rated current

A

0.26/0.16

0.26/0.16

0.26/0.16

0.52/0.29

0.52/0.29

0.52/0.29

Speed

U/min 1340/1040 1340/1040 1340/1040 1360/1020 1360/1020 1360/1020

Air capacity

m³/h 2250/1850 2050/1640 1850/1500 3800/3180 3400/2870 3150/2770

Sound pressure level

1)

dB(A)

52/46

53/48

55/49

55/50

55/51

58/54

Heating medium connection inch

R¾"

R1"

R1¼"

R¾"

R1"

R1¼"

Heating medium

Pump warm water or pump hot water up to max. 130 °C

Operating pressure

bar

16

16

16

16

16

16

Weight

kg

24

26

27

31

34

36

Type

BG 80 - 2

BG 80 - 3

BG 80 - 4 BG 100 - 2 BG 100 - 3 BG 100 - 4

Electrical connection

V

400/3N~

400/3N~

400/3N~

400/3N~

400/3N~

400/3N~

Frequency

Hz

50

50

50

50

50

50

Power consumption

kW

0.42/0.28

0.42/0.28

0.42/0.28

0.76/0.47

0.76/0.47

0.76/0.47

Rated current

A

0.76/0.46

0.76/0.46

0.76/0.46

1.50/0.81

1.50/0.81

1.50/0.81

Speed

U/min

880/670

880/670

880/670

870/650

870/650

870/650

Air capacity

m³/h 5800/4400 5400/4300 4730/3700 9050/7400 8250/6620 7670/6180

Sound pressure level

1)

dB(A)

55/49

55/49

55/49

58/54

58/54

59/55

Heating medium connection inch

R1"

R1¼"

R1¼"

R1¼"

R1½"

R1½"

Heating medium

Pump warm water or pump hot water up to max. 130 °C

Operating pressure

bar

16

16

16

16

16

16

Weight

kg

44

47

51

58

60

68

Proper use

The units are designed exclusively for industrial and com-
mercial heating and insulation purposes on the basis of
their design and equipment.
The manufacturer assumes no liability for damage re-
sulting from non-compliance with manufacturer specifi-
cations and legal requirements, or if modifications are
made to the units.

*

Operation/handling which does not comply with
these instructions is prohibited!
In cases of non-compliance, we assume no liability
and the guarantee becomes null and void.

Customer Service and
Guarantee

For the guarantee to be valid, the purchaser or his cus-
tomer must completely fill out the "guarantee certificate"
enclosed with all units and send it back to REMKO GmbH
& Co. KG

.

The units are repeatedly tested at the production site to
ensure that they are working properly. If a malfunction
occurs that cannot be eliminated by the operating per-
sonnel, please contact your dealer or contract partner.