NATURAL GAS TO LP CONVERSION INSTRUCTIONS

Figure 3 - Gas Valve

15.

Remove adjustment screw by turning counterclockwise

. See Figure 4.

16.

Remove stainless steel Natural gas spring. See Figure 4.

NOTICE

Parts for steps 17, 18, 26, and 27 are located in

Honeywell LP gas conversion kit HW#393691 for

VR8200, VR8204, VR8300 and VR8304 gas valves.

17.

Insert Red LP gas spring. See Figure 4.

18.

Install new adjustment screw. Assure the screw top is

flush with the regulator top. See Figure 4.

19.

Turn pressure regulator adjustment screw clockwise

eleven (11) complete turns. (This is starting point

for manifold pressure.)

20.

Install manometer to pressure tap on outlet side of gas

valve. See Figure 3.

21.

Turn electric and gas supply ON.

NOTICE

Gas inlet pressure is between minimum of 11”

w.c.and maximum of 14” w.c.

22.

Check for gas leaks around all gas connections using

commercially available soap solution specifically made

for leak detection.

DANGER

Fire Hazard. Do not use matches, candles, open

flames, or other methods providing ignition source.

Failure to comply will result in death or serious

injury.

!

23.

While boiler is operating adjust manifold pressure

to 11” water column by turning pressure regulator

adjustment screw. Check for CO2 and CO levels to

assure proper operation.

24.

Turn OFF electric and gas supply.

25.

Remove manometer. Replace pressure tap cover screw

securely.

26.

Install black LP gas regulator adjustment cover screw

with o-ring. See Figure 4.

27.

Mount conversion label on gas valve.

28.

Turn electric and gas supply ON.

29.

Cycle boiler to ensure proper operation and lighting.

30.

Replace front panel.

31.

Fill out and affix conversion plate adjacent to

rating plate. Complete this step to provide proper

identification for customer service or technical support

issues.

CAUTION

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.
• Do not touch any electrical switch; do not use

any phone in your building.

• Immediately call your gas supplier from a

neighbor’s phone. Follow gas supplier’s

instructions.

• If you cannot reach your gas supplier, call the fire

department.

!

Table 3 - MAIN BURNER ORFICES

INPUT (Btuh) ORIFICE

QTY.

45,000

47

1

70,000

50

2

96,000

47

2

120,000

49

3

145,000

47

3

170,000

49

4

175,000
195,000

47

4

245,000

47

5

295,000

47

6