Installation

|

Table 2. Power Cord Ratings (continued)

Dell UPS Model and Voltage

Supplied Cord Set

Country

Rating

Power Cord

2700W

230V

CEE 7/7 Schuko to C19

16A

Europe (Schuko)

Yes

BS 1363 to C19

13A

United Kingdom (New)

Yes

GB2009.1 to C19

16A

China

Yes

C19 to C20 Jumper

16A

Europe/Australia

Yes

C19 to C20 Jumper

16A

China

Yes

BS 546 to C19

15A

United Kingdom(Old)

Optional

TI16S3 to C19

16A

Thailand

Optional

AS 3112 to C19

15A

Australia

Optional

IRAM2073 to C19

16A

Argentina

Optional

CEI 23-50 to C19

16A

Italy

Optional

KSC8305 to C19

15A

South Korea

Optional

IS 1293 to C19

16A

India

Optional

NBR 14136 to C19

16A

Brazil

Optional

C19 to C20 Jumper

16A

North America

Optional

L6-20P to C19

15A

North America

Optional

4

For models with a detachable power cord.

Plug the detachable UPS power cord into the input

connector on the UPS rear panel.

5

Plug the UPS power cord into a power outlet.

The UPS front panel display illuminates. The Dell startup screen changes to the UPS status
summary screen. The UPS front panel display shows the flashing Standby icon

.

6

Press the button on the UPS front panel.

After the startup is complete, the status icon changes to the appropriate icon based on the UPS
operating mode (see Table 4 on page 42).

7

On the UPS status summary screen, press the button to check for active alarms or notices.
Resolve any active alarms before continuing. See “Troubleshooting” on page 69.

If there are no active alarms, a “No Active Alarms” message appears.

8

Verify that the Normal icon

appears on the UPS status summary screen, indicating that the

UPS is operating normally and any loads are powered (see Table 4 on page 42).

9

If an optional EBM is installed, see “Configuring the UPS for an EBM” on page 54.