Installing the water heater, Additional considerations, Vent kit information – Paloma PH-28c Direct Vent User Manual

Page 12: Kits sold separately.), Kit part number

background image

Additional Considerations

Do Not install vent terminal under any patio or deck.

To help prevent moisture from freezing on walls and under
eaves, do not locate vent terminal on the side of a building
with prevailing winter winds.

To help prevent water lines from freezing do not locate vent
terminal on the side of a building with prevailing winter
winds.

Do Not terminate vent directly on brick or masonry surfaces.
A rust-resistant sheet metal backing plate
(1 x 1 foot) (30 x 30 cm) is recommended behind vent. (See
Figure.)

Do Not locate vent terminal too close to shrubbery, as flue
gasses may damage them.

Caulk all cracks, seams and joints within six (6) feet (1.8 m)
of vent terminal.

Caulk around thimble face plate for weather tight seal.

All painted surfaces should be primed to lessen the chance of
physical damage. Painted surfaces will require maintenance.

Insulate vent pipe of water heaters exposed to cold
conditions (attics, crawl spaces, etc.) with inflammable
material to help prevent moisture from accumulating in vent
pipe. The insulation should be rated for the temperature and
should not contain substances that corrode the vent pipe.

Do Not extend exposed vent pipe of water heaters outside of
building.

Guard vent against accidental contact with people and pets.

WARNING

:

Moisture in the flue gas will condense as it

leaves the vent terminal. In cold weather this condensate can
freeze on the exterior wall, under the eaves and on
surrounding objects. Some discoloration to the exterior of
the building is to be expected. However, improper location
or installation can result in severe damage to the structure
or exterior finish of the building

Inside
Corner

Caulk

6’ (1.8 m)

Caulk Zone

If soffit vent is too close,
block off and install new
vent at another location.

Caulk

Caulk

Rising moisture will
collect under eaves.

6’

4’

1 ft. sq. (30 x 30 cm) sheet metal plate on
brick or masonry surface, recommended.

(1.8 m)

6’ (1.8 m)
Caulk

zone or to edge of window

etc.,starting within 6’ (1.8 m).

RTV silicone caulk

(1.2 m)

12

Installing the water heater.

17 1/2“
Long

Vent Kit Information

( Kits sold separately.)

Vertical Termination

Adapter

Faceplate

Air Intake Tee -

Heat Fab

Air Intake Tee - Pro-

Tech or Z-Flex

Air Intake/ Vent

Termination

Adapter

12” or 36” Long

4”/7” Concentric

Pipe

Vent Outlet

Termination for

Vertical Installation

Self Tapping Screw

Kit Part Number

28-20032HHT

Qty

28-20033VHT

Qty

28-20034HPT

Qty

28-20035VPT

Qty

12” x 12” Faceplate

12” Long - 4”/7”
Concentric Pipe

Horizontal Termination
Adapter

Air Intake Tee-Heat
Fab

Self Tapping Screws

2

1

1

1

8

36” Long - 4”/7”
Concentric Pipe

Vertical Termination
Adapter

Air Intake Tee-Heat Fab

Self Tapping Screws

Vertical Outlet
Termination

1

1

1

8

1

12” x 12” Faceplate

12” Long - 4”/7”
Concentric Pipe

Horizontal Termination
Adapter

Air Intake Tee-Pro Tech

Self Tapping Screws

2

1

1

1

8

36” Long - 4”/7”
Concentric Pipe

Vertical Termination
Adapter

Air Intake Tee-Pro Tech

Self Tapping Screws

Vertical Outlet
Termination

1

1

1

8

1