Operator Interface

DIGITAL ROOM SENSOR

9

LCD Backlight Test Screens

To select the third option—
BACKLTtouch

while at the Sensor Confi guration
& Test Screen
(Figure 11). This
option allows you to control
when the LCD backlight turns
on and off. You can confi gure the
backlight to stay on at all times,

remain off at all times, or to come
on when any button is touched on
the sensor.

To exit this screen, touch

play>

.

Thermistor Averaging Screen

To select the fourth and fi nal op-
tion—THRM AVG—, while at
the Sensor Confi guration & Test
Screen
(Figure 11), touch simul-
taneously below the

and

buttons. (See

Figure 10 which shows where to
touch to access this option.)

This option allows you to set the
rate—from 1-15 seconds—at
which the sensor takes a new
temperature reading. Touch <>
to increase the number of seconds
and touch <> to decrease the
number of seconds.

To exit this screen, touch

play>

.

NOTE: The sensor takes the average of the last 10 readings based

on the number that is entered in this screen. For example,
if you want a 3-second sample, the sensor will take the
average of the last 10 readings every 3 seconds over a
30-second span. Therefore, if you have your sensor next
to an outside doorway, you would want to enter a higher
number for your sample to give a more accurate read-
ing for the room temperature in case the outside door is
opened often.

Appendix

Figure 14: Backlight Test
& Confi guration Screen

Figure 15: Temperature
Averaging Screen

Display Options - Temperature/Setpoint

To access the Display Options
Screen
, while at the Thermistor
Averaging Screen
, (Figure 15),
touch the

button.

This option allows you to set the
main screen display. Touch <>
to display the Cooling/Heating

Setpoint on the Main Display
Screen
. Touch <> to display
the current room temperature on
the Main Display Screen. The
default is temperature.

If the Setpoint option is chosen,
when the unit is in the Cooling
Mode, the Cooling Setpoint
will appear on the Main Display
Screen
. When the unit is in the
Heating Mode, the Heating Set-
point will appear on the Main
Display Screen
. When the unit
is in Unoccupied Mode or Vent
Mode, the setpoint that appears
on the Main Display Screen will
be half way between the Cooling
and Heating Setpoint.

To exit this screen, touch

.

Figure 16: Address
Screen

DSPLY OPTIONS

TEMPERATURE

UP = SETPOINT

DOWN = TEMP