SPECIFICATIONS
Capacity
VA
1000VA
1200VA
1500VA
2000VA
3000VA
Input
Voltage
100VAC, 110VAC, 120VAC, 220VAC, 230VAC or 240VAC ±25%
Frequency
50Hz or 60Hz ±5%
Output
Voltage (Batt.
Mode)
100VAC, 110VAC, 120VAC, 220VAC, 230VAC or 240VAC ±10%
Frequency
50Hz or 60Hz ±1Hz
Waveform
Modified sine wave
Transfer Time
Less than 6ms (typical)
Battery
Battery Type
12V/7AH*2Pcs
12V/7AH*4Pcs 12V/9AH*4Pcs
Recharge Time
5 hours to 90% of full capacity
Indicator
LCD
LCD indicator for line-on, battery back-up, AVR protection,
load and battery level, overload and UPS cut-off
Alarm
Battery Back-up
Sounding every 3 seconds
Battery Low
Sounding every 1 second
Overload
Continue beeping sound
Protection
Overload
Fuse & current limited
Short Circuit
Fuse & current limited & cut-off
Batt. Low Cut-off
No battery drain after cut-off
Physical
Dimension,
D*W*H
390*182*285
Environment
Operating
Temperature
32℉-104℉ at full load, 0~90% relative humidity (non-condensing)
Noise Level
Less than 40db (at 1 meter)
Interface
USB&RS-232
Communication port
Software
imate
- 10 -
SYSTEM CONCEPT
The purpose to present this chapter is to give you more precise conception
about how UPS works..
1. Block Diagram
AVR.
INV.
CHA.
N.F.
N.F.
INPUT
OUTPUT
Fig. 1 shows how UPS works.
2. Normal Operation
There are two main loops when AC Utility normal the AC output loop and the
battery charging loop. The AC output gets power from AC utility input and
pass through AVR to support power to load. In the same time, the AC utility
input is converted by AC/DC CHA and support charging power to charge
batteries.
AVR.
INV.
CHA.
N.F.
N.F.
INPUT
OUTPUT
Fig. 2 shows how the UPS works when AC Utility normal.