Screen sheet, Make a center hole. ф 3.1 (ф 3.2 max.) – MovinCool 30HU User Manual
Page 2

2
3-1. Cut out the screen sheet on the last page of this manual (See Fig. 4). Confirm the reference
hole on the sub control box to be matched with the reference hole on the screen sheet.
3-2. Match the screen sheet’s reference hole to the sub control box’s reference hole and position
the screen sheet as shown in Fig.5. Use adhesive to temporarily hold the screen sheet.
Mark a center hole position on the sub control box, then remove the screen sheet.
Make a center hole (recommended size: Ф 3.1 (Ф 3.2 max.)). Remove all metal dust.
3- 3. Match the compressor relay’s reference hole to the sub control box’s reference hole in the
3- 4. Install the left front panel and left rear panel in the reverse order of the removal steps.
direction shown below (See Fig. 6). Attach the compressor relay with two supplied screws at
the torque of 1.3 ± 0.1 ft.lbf (1.8 ± 0.2 N•m). Connect the compressor wires to the compressor
relay connectors as shown in the table.
Fig. 4
Fig. 5
Fig. 6
Last page of this manual
Screen Sheet
Reference Hole
Reference Hole
Center Hole
Screen Sheet
Compressor Relay
Reference Hole
Center Hole
Center Hole
Top
Reference Hole
A1
A2
4
6
2
1
3
5
Sub Control Box
Sub Control Box
3. Installation of New Compressor Relay
29.5 mm
29 mm
TOP
Cut
Compressor Wire No. Relay Connector Code
U2
2
4
6
1
3
5
A1
A2
V2
W2
R
S
T
22
34
TOP
34 mm
52 mm
Screen Sheet
TOP
Cut
Make a center hole.
Ф 3.1 (Ф 3.2 max.)
Reference Hole