Control settings – Delta Temperature Controller DTD Series User Manual

Page 3

background image

Input Sensor Type

Display

Temperature Range

0V ~ 5V input

-999 ~ 9,999

0 ~ 70mV input

-999 ~ 9,999

Cu50 type

-50

o

C ~ 150

o

C (-90.0

o

F ~ 302.0

o

F)

Pt100 type 2

-99.9

o

C ~ 600.0

o

C (-99.9

o

F ~ 999.9

o

F)

Pt100 type 1

-200

o

C ~ 600

o

C (-360

o

F ~ 1,112

o

F)

JPt100 type

-20.0

o

C ~ 400.0

o

C (-36.0

o

F ~ 752.0

o

F)

Thermocouple TXK type

-200

o

C ~ 800

o

C (-360

o

F ~ 1,472

o

F)

Thermocouple U type

-200

o

C ~ 500

o

C (-360

o

F ~ 932

o

F)

Thermocouple L type

-200

o

C ~ 850

o

C (-360

o

F ~ 1,562

o

F)

Thermocouple B type

100

o

C ~ 1,800

o

C (180

o

F ~ 3,272

o

F)

Thermocouple S type

0

o

C ~ 1,700

o

C (0

o

F ~ 3,092

o

F)

Thermocouple R type

0

o

C ~ 1,700

o

C (0

o

F ~ 3,092

o

F)

Thermocouple N type

-200

o

C ~ 1,300

o

C (-360

o

F ~ 2,372

o

F)

Thermocouple E type

0

o

C ~ 600

o

C (0

o

F ~ 1,112

o

F)

Thermocouple T type 2

-99.9

o

C ~ 400.0

o

C (-99.9

o

F ~ 752.0

o

F)

Thermocouple T type 1

-200

o

C ~ 400

o

C (-360

o

F ~ 752

o

F)

Thermocouple J type 2

-99.9

o

C ~ 999.9

o

C (-99.9

o

F ~ 999.9

o

F)

Thermocouple J type 1

-200

o

C ~ 1,200

o

C (-360

o

F ~ 2,192

o

F)

Thermocouple K type 2

-99.9

o

C ~ 999.9

o

C (-99.9

o

F ~ 999.9

o

F)

Thermocouple K type 1

-200

o

C ~ 1,300

o

C (-360

o

F ~ 2,372

o

F)

Control Settings!

Setting up Control Mode

In the operation mode, press

for more than 3 seconds and PV will display the parameter

. Press

for 4 times to display

the parameter

. The default setting of this parameter is “On/Off control”

. Use

to select PID control

, PID

programmable control

or manual control

. Press

again and display the parameter

for selecting the control

method. You can select heading (default)

or cooling

. Press

to return to the operation mode.

Setting up RUN and STOP

In the operation mode, press

and display parameter

. The default is RUN

. Use

to select STOP

. Press

to complete the setting and the output will be disabled.

Setting up On/Off Control Parameters

Press

in the operation mode. If DTD is in On/Off heating mode, the PV will display

; if in On/Off cooling mode, the PV will

display

. Modify these parameters to set up the hysteresis of On/Off. The default setting is 0 (without hysteresis). When the output

reaches SV, the control output will be disabled. When the input is bigger (cooling) or smaller (heating) than the SV and hysteresis, the
control output will be enabled. When the On/Off hysteresis is not 0, the control output will be like the diagrams below.

Hysteresis

HtS

OFF

ON

OFF

ON/OFF Control for Heating

SV

Hysteresis

CtS

OFF

ON

ON

ON/OFF Control for Cooling

SV

Setting up PID Parameters

When in PID control mode, you have to first decide the On/Off cycle time for the control output, i.e. the control cycle. Press

in the

operation mode and PV will display

. Press

5 times to display the parameters of heating control cycle

or cooling

control cycle

. Set up the cycle depending on the reaction speed of the control system. In principle, the faster the reaction, the

shorter the cycle and more accurate the control. A short control cycle indicates that there will be more times of On/Off. If you adopt relay
output, the short cycle will shorten the life span of the relay. Therefore, it is recommended that you adopt voltage output in the PID control
mode. The default setting of the control cycle is 20 seconds.

3