beautypg.com

Maytag WMH76719CB Dimension Guide User Manual

Page 2

background image

VENTING REQUIREMENTS

Because Whirlpool Corporation policy includes a continuous commitment to

improve our products, we reserve the right to change materials and specifications

without notice.

Dimensions are for planning purposes only. For complete details, see

Installation Instructions packed with product. Specifications subject to

change without notice.

Page 2 of 2

Rectangular to Round Transition:

Recommended Standard Fittings
The following length equivalents are for use when figuring vent

length. See the examples in “Recommended Vent Length.”

NOTE: The minimum 3" (7.6 cm) clearance must exist

between the top of the microwave oven and the

rectangular to round transition piece so that the damper

can open freely and fully.

27" (68.6 cm) models

A. Roof cap

B. 6" (15.2 cm) min. diameter round vent

C. Elbow (for wall venting only)

D. Wall cap

E. 31⁄4" x 10" to 6" (8.3 x 25.4 cm to 15.2 cm)

rectangular to round transition piece

F. Vent extension piece, at least 3" (7.6 cm) high

A. Rectangular to round transition piece: 31⁄4" x 10" to 6" = 5 ft

(8.3 x 25.4 cm to 15.2 cm = 1.5 m)

B. Roof cap: 31⁄4" x 10" = 24 ft (8.3 x 25.4 cm = 7.3 m)

C. 90° elbow: 3 " x 10" = 25 ft (8.3 x 25.4 cm = 7.6 m)

D. 90° elbow: 6" = 10 ft (15.2 cm = 3 m)

E. Wall cap: 31⁄4" x 10" = 40 ft (8.3 x 25.4 cm = 12.2 m)

F. 45° elbow: 6" = 5 ft (15.2 cm = 1.5 m)

G. 90° flat elbow: 31⁄4" x 10" = 10 ft (8.3 x 25.4 cm = 3 m)

Recommended Vent Length
A 3

1

4

" x 10" (8.3 x 25.4 cm) rectangular or 6" (15.2 cm) round

vent should be used.
The total length of the vent system including straight vent,

elbow(s), transitions and wall or roof caps must not exceed

the equivalent of 140 ft (42.7 m) for either type of vent. See

“Recommended Standard Fittings” section for equivalent

lengths.
For best performance, use no more than three 90° elbows.
To calculate the length of the system you need, add the

equivalent lengths of each vent piece used in the system.

See the following examples:

3

1

4

" x 10" (8.3 x 25.4 cm) vent system = 73 ft

(22.2 m) total

A. One 3

1/4

" x 10" (8.3 x 25.4 cm) 90° elbow = 25 ft (7.6 m)

B. 1 wall cap = 40 ft (12.2 m)

C. 2 ft (0.6 m) + 6 ft (1.8 m) straight = 8 ft (2.4 m)

6" (15.2 cm) vent system = 73 ft (22.2 m) total

A. Two 90° elbows = 20 ft (6.1 m)

B. 1 wall cap = 40 ft (12.2 m)

C. 1 rectangular to round transition piece = 5 ft (1.5 m)

D. 2 ft (0.6 m) + 6 ft (1.8 m) straight = 8 ft (2.4 m)

If the existing vent is round, a rectangular to round transition

piece must be used. In addition, a rectangular 3" (7.6 cm)

extension vent between the damper assembly and rectangular

to round transition piece must be installed to keep the damper

from sticking.

LOCATION REQUIREMENTS
Special Requirements

For Wall Venting Installation Only:

Cutout must be free of any obstructions so that the vent

fits properly, and the damper blade opens freely and fully.

For Roof Venting Installation Only:

If you are using a rectangular to round transition piece, 3"

(7.6 cm) clearance needs to exist above the microwave

oven so that the damper blade can open freely and fully.

See “Rectangular to Round Transition” illustration in

“Venting Design Specifications” section.

A

B

C

E

F

D

3" (7.6 cm)

A B

C

6 ft (1.8 m)

2 ft

(0.6 m)

A B

C D

6 ft (1.8 m)

2 ft

(0.6 m)

A B C

D E F G

Ref. W10724870A

05/15