Owner’s manual, Air for combustion and ventilation, Continued – Desa PCVDR24 RGA User Manual
Page 5
5
901747
OWNER’S MANUAL
DETERMINING FRESH-AIR FLOW FOR APPLIANCE LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space:
Includes the room in which you will install appliance plus any adjoining rooms with doorless passageways or ventilation grills
between the rooms.
1.
Determine the volume of the space (length x width x height).
Length x Width x Height = _________________ cu. ft. (volume of space)
Example:
Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.
2.
Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.
_____________ (volume of space)
÷
50 cu. ft. = (maximum Btu/Hr the space can support)
Example:
2560 cu. ft. (volume of space)
÷
50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)
3.
Add the Btu/Hr of all fuel burning appliances in the space.
Gas fireplace logs
_____________ Btu/Hr
Gas water heater*
_____________ Btu/Hr
Gas furnace
_____________ Btu/Hr
Vented gas heater
_____________ Btu/Hr
Vent-free heater
_____________ Btu/Hr
Other gas appliances* + _____________ Btu/Hr
Total = _____________ Btu/Hr
* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
4.
Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
_____________ Btu/Hr (maximum the space can support)
_____________ Btu/Hr (actual amount of Btu/Hr used)
Example:
51,200 Btu/Hr (maximum the space can support)
95,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-
ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.
B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.
C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.
AIR FOR
COMBUSTION AND
VENTILATION
Continued
Example:
Gas water heater
40,000 Btu/Hr
Gas fireplace logs +
55,000 Btu/Hr
Total
=
95,000 Btu/Hr
Continued
WARNING: If the area in which the appliance may be operated is smaller than that defined as an unconfined
space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one
of the methods described in the
National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3 or applicable local codes.