2 troubleshooting, 3 water quality – Kemppi KempCool 40 User Manual
Page 9

EN
3.2 Troubleshooting
Problem
Cause
Action
Insufficient cooling
capacity
The heat exchanger and/or air filter is
dirty. Clean the components.
Clean the components.
Cooling air temperature is too high.
Check the air temperature.
Cooling system is overloaded.
Remove any extra cooling consumers.
The coolant temperature is too high
(> 40 °C).
Check thermoregulator setting. Replace if
necessary.
Pump does not start
Thermal protection of the pump motor
has gone off.
Check the fuses.
Flow alarm is on (the
red warning light on the
front panel)
The coolant level is too low.
Check the cooling system for leaks and add more
coolant if needed.
3.3 Water quality
Subject to the equipment to be cooled or heat-balanced, certain requirements have to be met
by the cooling water regarding purity. The degree of the water`s contamination, as well as the
size and construction of the heat-exchanging- or -balancing plant determine the process most
suitable for the application of additives and/or care of the water-supply in question. You can
use normal tap water when filling the tanks.
With deviating water-quality, we recommend using the services of consultants, or to have a
water analysis or water sample sent to us.
Kemppi is not liable for any malfunctions or damages arising from deviating water qualities.
When employing chillers at temperatures below + 8°C, an anti-freeze medium must be added.
7
© Kemppi Oy / 1204