Water quality considerations – Herrmidifier Herrmidicool Technical Guide User Manual
Page 14

the calculated load.
10. Air consumption shall be a maximum of 12
SCFM free air per 100 pounds of water 
atomized. Compressor shall include an 
appropriate safety factor. 
 
D. OPERATING SEQUENCE 
1. On a fall in relative humidity (in the space or
return air duct), the space or return air 
transmitter shall send a signal to the controller. 
2. A discharge high limit controller shall supply a
signal to the controller.
3. The controller shall have an adjustable setpoint
for both the return air (or space) and high limit, 
and shall compare the sensed relative humidity 
to the respective setpoints. 
4. The controller shall output a proportional signal
based on the humidity input, which is closest to 
its respective setpoint. 
5. On multi-manifold applications, the manifolds will
be modulated in parallel or stages depending on 
the application. 
6. On DDC system, sensors and control algorithm
provided by other. 0-100% demand signal 
provided to Herrmidifier Control Cabinet. 
7. The system will automatically shutdown if the
airflow switch, located in the discharge duct, is 
deactivated. 
8. A power failure or compressor failure will
automatically shut the system down.
9. f water pressure is lost or reduced, the atomizing
heads shall sputter with no drippage. Complete 
loss of water supply will cause the atomizing 
heads to blow air only. 
PART 3 EXECUTION 
 
A. GENERAL 
1. Install system(s) as detailed on the drawings
and/or as recommended by the manufacturer. 
Shop drawings, indicating manifold sizes and 
atomizing head capabilities shall be provided by 
manufacturer. Certified independent air 
consumption (at various output levels) and noise 
data shall be available. 
2. Manufacturer's
representative shall provide
analysis, design and startup support of the 
custom engineered humidification system(s). 
3. Factory personnel will start system. 
4. Compressed air shall be oil free and dry. Air 
shall be filtered to a maximum of 0.3 micron. 
Dryers and aftercoolers "applied" as the 
compressor manufacturer recommends. 
5. Water treatment, if supplied, demonstrates a
satisfactory water supply to the humidifier.
 
Herrmidicool Systems are manufactured by: 
Herrmidifier 
101 McNeill Road 
Sanford, NC 27330 
 
 
 
 
 
 
 
Water Quality Considerations 
The Herrmidicool atomizing head was developed over 
40 years ago and, because of its self-cleaning capability, 
has operated on water as hard as 68 grains/gal. with 
routine maintenance. However, when atomized water 
droplets evaporate, they leave behind mineral residue in 
the form of a fine dust. In an environment such, this dust 
may not be a concern since the printing operation may 
put more contaminants in the air than atomization. In a 
computer room or cleanroom, mineral dust could be 
disastrous. 
 
Historically, water quality under 50 ppm Total Dissolved 
Solids (TDS) and balanced on the Langelier Saturation 
Index (LSI: -0.5 to +0.5), has been used successfully in 
general office applications. However, the increased 
sensitivity to IAQ will further restrict applications where 
raw water can be used. The minerals can be removed 
from the water or from the airstream downstream of the 
humidifier. ALWAYS send a copy of the water analysis 
from your site to Herrmidifier for review if you plan on 
using raw water. Many sites have demineralized water 
available for use in the humidification equipment. If this 
is the case, simply confirm the water supply has been for 
the humidifier has been demineralized or will be 
provided as part of the humidification project. Your 
application may contain sensitive equipment that 
dictates what water treatment path is followed. Planning 
in the design stages is far easier than reworking after the 
fact! 
 
If according to the results of your consultation with 
Herrmidifier, the water is deemed unusable in raw form, 
the water can be treated through a variety of techniques 
including nanofiltration, reverse osmosis, deionization or 
a combination thereof. Depending on your application, 
Herrmidifier can suggest the most cost effective method 
to solve your water related problems. The proper 
selection of water treatment for a Herrmidicool system is 
a very important step in the design process, and should 
not be discounted. 
HERRMIDICOOL Technical Manual