Flowserve TRS 5-6 User Manual
Page 9

9
Technical Data
Type-approval no.
DIN · STW (STB) · 985 93S
Input
3 terminals for the connection of one resistance thermometer (Pt 100):
TRG 5-5..., PN 40 – 160, T
max
251 °C – 540 °C
Output
2 volt-free relay contacts.
Max. contact rating with switching voltages of 24 V, 115 V and 230 V a. c.:
4 A resistive, 0.75 A inductive, cos
ϕ
0.5.
Max. contact rating with a switching voltage of 24 V d. c.: 4 A
Contact material silver, hard-gold plated.
Temperature range
Temperature limits adjustable in steps of 2 °C within a range of 30 °C to 540 °C by a
code switch.
Switching hysteresis
– 3 °C
Indicators and adjustors
2 red LEDs
ALARM
1 green LED “
POWER
ON
”
1 button
TEST
I
1 toggle switch
TEST
II /
INSPECTION
8 LEDs and 1 eight-pole code switch for setting the limit temperature.
Mains supply
230 V +/– 10 %, 50/60 Hz
Special voltage: 115 V +/– 10 %, 50/60 Hz or 24 V +/– 10 %, 50/60 Hz
Power consumption
5 VA
Protection
TRS 5-6 b: IP 20 to DIN EN 60 529
TRS 5-6 c: IP 10
TRS 5-6 d: IP 10
Permissible ambient temperature
TRS 5-6 b: 0 – 55 °C
TRS 5-6 c: 0 – 70 °C
TRS 5-6 d: 0 – 70 °C
Case materials
TRS 5-6 b: Base: ABS plastic, black. Cover: polystyrene, highly shock-resistant,
stone grey. Fig. 5, Fig. 6
TRS 5-6 c: Front panel: Aluminium. Fig. 7
TRS 5-6 d: Front panel: Aluminium. Fig. 7
Weight
TRS 5-6 b: approx. 1.0 kg
TRS 5-6 c: approx. 0.8 kg
TRS 5-6 d: approx. 0.8 kg
Explanatory Notes