Wiring, Terminal box – Flowserve NRGS 16-4 User Manual
Page 14
14
Wiring
Terminal box
Use screened cable type I– Y (St) Y 2x 2x0.8mm ² or LIYCY 4x 0.5mm ² for wiring.
1. Unscrew screw
. Fig.3
2. Remove terminal box from level electrode, leaving the insulating rubber plate
on the contact
plate
.
3. Remove cover
.
4. Press connecting plate
out of the upper part of the terminal box
.
The electrode terminal can be turned in steps of 90°.
5. Detach cable gland
and cable strain relief
from the upper part of the terminal box
.
6. Run cable through cable gland
and upper part of the terminal box
and wire the terminal of the
connecting plate
according to the wiring diagram (see Fig. 8).
7. Press connecting plate
into the upper part of the terminal box
and align the cable.
8. Fix cable with cable strain relief
and cable gland
firmly into position.
9. Replace cover
and insert screw
.
10.Put upper part of the terminal box onto the level electrode and fix it with screw
.
If several level electrodes are to be installed in one steam boiler or vessel we recommend labelling the
terminal box with the electrode type.