Installation – Flowserve NRG 16-50 User Manual
Page 16
6
Installation
NRG 16-50, NRG 17-50, NRG 19-50, NRG 111-50, step 1
. Screw electrode tip
4
into measuring electrode
1
.
Fig. 8
. Carefully determine required measuring length of electrode.
3. Mark length of electrode tip
4
.
4. Unscrew electrode tip
4
from measuring electrode
1
and cut tip.
5. After visual inspection screw electrode tip
4
into measuring electrode
1
. Slide spring
3
along
electrode tip
4
so that its end completely enters the small hole
2
.
NRG 16-50, NRG 17-50, NRG 19-50, NRG 111-50, step 2
6. Check seating surfaces.
Fig. 12
7. Place joint ring
5
onto seating surface
6
of the electrode.
Fig. 9
8. Apply a light smear of silicone grease (e. g. WINIX
®
50) to electrode thread
7
.
9. Screw level electrode into threads or flange provided on vessel and tighten with a 4 mm open-end
spanner.
The torque required
when cold is 160 Nm.
NRG 16-50 F, NRG 17-50 F, NRG 19-50 F, additional information
If one level electrode NRG ...-50 is installed together with one level electrode, one level switch or
transmitter (with aluminium terminal box) in a single protection tube or level pot, please observe the
following:
. Mount the first level electrode as specified in the pertinent installation manual.
When installing level electrode NRG ...-50 F, please observe the following instructions:
. Unscrew screws
g
and remove housing cover
i
.
Fig. 14. The arrow on the name plate points
towards this cover..
. Remove cable lugs from terminal lugs.
Fig. 15
3. Loosen nut
j
with a 9 mm spanner, but do not remove!
Fig. 15
4. Screw in level electrode as described in items 6 – 9.
5. Turn terminal box into desired position (+/– 80°).
The terminal box can now be turned through +/– 180°.
6. Tighten nut
j
with a torque of
25 Nm.
7.
Plug cable lugs onto terminal lugs.
8. Mount housing cover
i
and tighten screws
g
.
WINIX
®
50 is a registered trademark of WINIX GmbH, Norderstedt