Operation and maintenance – Flowserve 93 Series PULSAIR III User Manual
Page 7

19860-C
Series 93 PULSAIR III Digital Electronic Positioner Installation, Operation and Maintenance
7
Flow Control Division
Worcester Controls
and then clockwise until sensor 1 trips. The milliammeter
indication changes from
≥ 3 mA to a ≤ 1 mA reading.
4. Tighten the two mounting scrrews to 15 mA, and return to 20
mA to verify that the cam trips the sensor, and the milliammeter
reading changes from a
≥ 3 mA to a ≤ 1 mA.
5. Remove the milliammeter and power supply leads from termianl
positions 6 and 7, and attach them to termianl positions 3 and 4.
6. Adjust the input signal to 4 mA and verify that the cam trips the
sensor and the milliammeter reading changes from a
≥ 3 mA to
a
≤ 1 mA reading.
7. If the milliammeter reading does not change, and continues to
show an
≥ 3 mA reading, loosen the cam assembly mounting
screws and adjust the cam as necessary.
8. Repeat the adjustment and set procedure until you can supply a
4 mA or a 20 mA signal and have the appropriate sensor trip.
Operation and Maintenance
Refer to Technical Reference Manual (Part No. 19990) for detailed
operation and maintenance information.