Apex 5000 Positioner
Installation, Operation and Maintenance Instructions
CONTROLS
Accord Controls
765 South 100 East
Phone: 801 373 4576
A Unit of Flowserve Corporation
Provo, Utah 84606-6160
Facsimile: 801 489 2591
www.accord-controls.com
Class I, Division 2, Applications must be installed as specified in NEC Section 501-4 when barriers are not used.
(Refer to ANSI/ISA RP12.6 for guidance on installation).
Electrical Specifications:
Field Installation:
All input options can be added/changed
in the field without removing positioner cover. Figures 3
and 4 (5100 and 5200/5600 respectively) show mounting
information and location of terminal connections.
Caution:
If I/P Module is installed in explosive atmosphere,
disconnect power prior to removing cover to avoid
personal injury.
1. Remove supply pressure and input signal connection.
2. Remove old I/P Module or pneumatic manifold and
associated hardware.
3. Following applicable figure, install new I/P Module and
associated hardware. Be sure O-rings are in place.
4. Make electrical and pneumatic connections. Do not use
Teflon tape on supply connection fitting. Use only a
liquid or paste non-hardening pipe sealant on
the threads.
5. For intrinsically safe applications (Model 5400 only)
refer to Figure 1 for barrier information and schematics.
6. All I/P Modules are factory calibrated and should not
require adjustment. However, it is recommended that
calibration be checked (see “I/P Module Calibration”).
7. Install cover.
Page 4 of 8
Parameter
Model 5100
Model 5200
Model 5300
Model 5400
Model 5600
Max. Voltage VDC
30
30
28
30
28
Min. Voltage VDC
6
5.5
5.5
5.5
5.5
Max. Current (mA)
50
125
93.3
125
93.3
C (Micro Farad)
1
1
1
1
1
L (Mili Henry)
1
1
1
1
1
Hazardous Locations
Exp. Proof
Exp. Proof
Intrinsically Safe
Intrinsically Safe
CL l,ll, Div 1
EEx d llB+H2
CL l,ll Div 1
EEx ia llC T4
Non-incendive
T6-40 to +40C
Groups B-G
CL l, Div 2
T5-40 to +75C
Groups A-D
T4-40 to 110C
Agency Approval
FM/CSA
SCS
FM/CSA
SCS