Limitorque
®
L120-190 through L120-2000 FCD LMENIM1203-00 – 10/11
flowserve.com
5.3.1 Mounting Base
The mounting hole sizes and quantities are as detailed in Table 5.1, below:
Table 5.1 – Mounting Base Dimensions
Actuator Size
Mounting Holes
Tap Size
ISO
Bolt Circle
ISO
Quantity
MSS
MSS
L120-190
8
3/4–10 x 1.13
M20 x 2.5 x 32
11.75
298 mm
L120-420
8
7
⁄
8
–9 x 1.75
N/A
14.0
N/A
L120-800 (Torque Only)
8
3/4–10 x 1.63
N/A
17.0
N/A
L120-800 (Thrust Only)
8
1.25–7 x 2.0
N/A
16
N/A
L120-2000 (Torque Only)
16
1–8 x 2.0
N/A
23.5
N/A
L120-2000 (Thrust Only)
12
1-1/2–6 x 3.0
N/A
18.0
N/A
5.3.2 Stem Acceptance
The maximum stem acceptance is provided in Table 5.2, below:
Table 5.2 – Maximum Stem Acceptance
Actuator size
Drive 2 Tapped
Drive 1 Bore
Drive 1 Key
inch
mm
inch
mm
inch
mm
L120-190
3.5
89
2.875
73
3/4 x 1/4
20 x 12
L120-420
5
127
4.25
108
1 x 3/4
28 x 16
L120-800
5
127
7
178
1 x 3/4
32 x 18
L120-2000
6.25
159
8.00
203
11/4 x
7
⁄
8
40 x 22
NOTE: For complete mounting dimensions, see sales brochure LMENBR1200.
5.4 Double Torque Switch
The torque switch is designed to protect the actuator in open and close directions.
Figure 5.1 – Double Torque Switch
NOTE: See Caution and Note on following page.