beautypg.com

Flowserve I-75 Interface User Manual

I-75 interface, Description

background image

Worcester Actuation Systems

1. Description

The I-75 Interface is designed to be used and mounted in the Series
75 Actuator as one of many standard options. Function of the I-75
Interface is to allow the Series 75 Actuator to be powered by a 120 or
240 VAC power supply, operated directly by any programmable
controller, microprocessor, and/or computer regardless of the output
rating of these devices. Depending on the control input to be used,
there are several options of the I-75 Interface:

These options are identified by the nameplate on the circuit board.

5V for 5 VDC input

XV for 12 VDC input

XX for 24 VDC input

15 for 120 VAC input

2. Installation of I-75 Interface Board into

Series 75 Electric Actuator

2.1 Check Kit for Parts:

Common Parts for Sizes 10-30 Actuators

Qty.

Name

1

Circuit Board Subassembly

1

Insulating Board

5-6

Washers (Nylon)

5-6

Grommets (Rubber)

5-6

Mounting Screws

5

Cable Ties

1

Wiring Label

1

Closed-End Splice

1

Wire - White

Additional Parts for Sizes 10-23 Actuators

Qty.

Name

1

Bracket - Right

1

Bracket - Left

2

Spacer (Bracket)

2

Mounting Screw (Spacer/Bracket)

Additional Parts for 240 VAC Option

Qty.

Name

2

Limit Switch

1

Lead Assembly - Gray

1

Lead Assembly - Blue

Additional Parts for Sizes 25, 30 Actuators

Qty.

Name

1

Mounting Bracket

2

Mounting Screw (Bracket)

Tools needed for assembly:

1

/

4

" Nut Driver,

1

/

8

" Screwdriver and Needle Nose Pliers.

FCD WCAIM2000-00

(Part 06094)

I-75 Interface

Installation, Operation and Maintenance Instructions

Figure 1