Flowserve DataFlo P Smart Positioner User Manual
Dataflo p smart positioner, Program mode, Functions
DataFlo P
Smart Positioner
Functions
FCD WCAIM2061-00 (Part 08987)
Program Mode
Abbreviation
Data Entry Parameter
Display
CodE
Security Code
CodE / 0000
Addr
Unit Address
Addr / 1-255
Ocur
Output Current Range
0-20 or 4-20 mA
Sdir
Setpoint Direction
riSE or FALL
SPrS
Split Range Start
0.0% to 99.9%
SPrE
Split Range End
0.1% to 100.0%
OPEn
Setpoint Ramp Time to Open
0 to 200 sec.
CLOS
Setpoint Ramp Time to Close
0 to 200 sec.
SFc
Setpoint Curve Function
Lin or FrE 1-4
dEbA
Positioner Deadband
0.1 to 10.0%
SPOS
Loss of Signal Position
0.0 to 100.0%
SPt
Loss of Signal Delay Time
0.0% to 9999 sec.
PPOS
Power On Position
0.0% to 100.0%
PPt
Power On Delay Time
0 to 9999 sec.
yA
Lower Rotation Limit
0.0 to 100.0%
yE
Upper Rotation Limit
0.0 to 100.0%
yCLS
Tight Valve Shutoff
yES or no
yOPn
Full Open Valve
yES or no
br
Brake-On Time
0.10 to 0.99 sec.
CyS
Run Time Cycles for Maintenance
CyCn
Accumulated Cycles
0–10 m cycles
AdE
Deviation Alarm Time
AHi
Upper Rotation Alarm
0.0% to 100.0%
ALo
Lower Rotation Alarm
0.0% to 100.0%
PrSt
Restore Default Parameter Values
yES or no
Worcester Actuation Systems