Automax buswitch, Profibus-dp – Flowserve BUSwitch-Profibus-DP User Manual
Page 3

 
 
 
 
 
 
LML0012-0 8/99
Page 3 of 6
©1999, Flowserve Corporation, Provo, Utah
Flowserve Corporation
Flow Control Division
Automax BUSwitch
TM
– Profibus-DP
765 South 100 East
Provo, Utah 84606
www.flowserve.com
Phone: 801 373 3028
Facsimile: 801 489 2228
Email: [email protected]
Figure 4
Special notes on the fieldbus cabling. 
Due to the high-speed communication capability of 
Profibus-DP networks, it is important to follow 
established specifications closely to ensure full 
communication capability. Governance of the 
physical level requirements is specified in the 
European Norm EN50170: "General Purpose Field 
Communication System.” To obtain the maximum 
communication capability it is highly recommended 
to only use type ‘A’ cable as defined in table one 
below. As a rule, data speed and maximum 
segment length are inversely related. At 9.6 kBaud, 
segment lengths up to 1200 meters are allowed. At 
12 MBaud the segment length falls to 100 meters. 
The following tables were obtained from The Rapid 
Way to Profibus-DP by Manfred Popp; available 
from the PROFIBUS Nutzerorganisation (PNO) as 
order number 4.072. To order, contact the Profibus 
Trade Organization (PTO) in your area. 
 
Line Parameters 
Line Type A
Line Type B
Impedance (
Ω)
135 to 165
100 to 130
Capacitance per 
unit length (pF/m) 
<30 <60
Loop resistance 
(
Ω/km)
110 ---
Core diameter 
(mm) 
0.64 >0.53
Core cross 
section (mm
2
)
>0.34 >0.22
Table 1
 
Recommended Line Lengths 
Transmission rate (kBaud) 
9.6
19.2 93.75
Line Type A
1200 1200 1200
Line Type B
1200 1200 1200
 
Transmission rate (kBaud) 187.5 
500
1500
Line Type A
1000
400
200
Line Type B
600
200
-
 
Transmission rate (kBaud) 1200 
Line Type A
100
Line Type B
-
Table 2
Adjustment of Switch Cams
1. Loosen five captive cover screws and remove
lid, turning slightly while lifting.
2. Place the actuator in the clock-wise (CW)
position and apply 24 VDC to the Profibus-DP 
Interface Card. 
3. Push down on the top cam (figure 4)
until it clears the splined coupler and 
rotate clockwise until the CW LED (red) 
is illuminated. 
4. Release the cam and insure that it
fully engages the spline.
5. Place the actuator in the counter-
clockwise (CCW) position.
6. Pull up on the lower cam (figure 4)
until it clears its splined coupler and 
rotate counter-clockwise until the 
CCW LED (green) is illuminated. 
7. Release the cam and insure that
it fully engages the spline.
8. Cycle the actuator to insure that
each LED is illuminated at the appropriate time. 
Some minor readjustment might be necessary. 
9. Clean base, lid flanges, and replace lid on base.
Make sure wires are NOT caught between 
flanges, and tighten captive screws. 
 
 
BUSwitch Configuration 
 
Configuration of the BUSwitch is accomplished 
through three main steps; physically connecting to 
the network, setting the device address / operating 
mode and sending operating parameters over the 
Profibus segment. The physical connection to the 
segment was covered previously in this document. 
Setting of the device address and operating mode is 
accomplished by a printed circuit board (PCB) 
mounted switch assembly (refer to figure three). 
The switch assembly has eight numbered positions, 
each of which can be set to either ON or OFF. 
Switch #1 sets dual coil operation when in the ON 
position, or single coil operation when placed in the 
OFF position. Switches 2 through 8 are used to set 
the address of the BUSwitch on the Profibus 
segment. The switches are a binary representation 
of the address with switch number 2 being the most 
significant digit and switch number 8 being the least 
significant digit. The decimal value of each switch 
when set to the ON position is as follows. 
 
Switch
#
2 3 4 5 6 7 8
Decimal
Value 64 32 16 8 4 2 1
Table 3
