Flowserve 2 Series P0 Type Kämmer Pneumatic Actuator User Manual
Page 3
3
Flow Control Division
Kammer Control Valves
(for pneumatic positioners, 0.2 - 1.0 bar or corre-
sponding split-range values; for IP positioners, 4-20
or 0-20 mA).
4.3
Check all air connections for leaks.
4.4
Tighten packing nut (see table 1).
NOTE:
An excessively tightened gland nut can cause
excessive packing wear and can hinder the free move-
ment of the plug stem.
4.5
Check fail-safe position. To do this, close supply
pressure and observe whether the valve opens or
closes as defined.
4.6
After use at fluctuating temperatures, re-tighten all
bolt connections and check for leaks.
5
MAINTENANCE
Check valves for correct functioning at regular inter-
vals (at least once every 6 months) as follows. This
check can be made when installed and in many
cases without interrupting production. If internal de-
fects are suspected, see section „Disassembly and
Assembly of Valve“.
5.1
Examine gaskets for leaks and if necessary re-tighten
bolts (see Fig. 1).
5.2
Check bellows gasket and test connection - if present
- for external leaks.
5.3
Check valve for damage caused by corrosive residues
or corrosive vapours.
5.4
Clean valve/actuator and repaint as necessary.
Warning:
To prevent a buildup of electrostatic charge
clean the actuator/valve with a damp cloth only.
5.5
Check gland nut for correct torque (see table 1).
NOTE: An excessively tightened gland nut can cause
excessive packing wear and can hinder the free move-
ment of the plug stem.
5.6
If possible, open and close valve and check for maxi-
mum stroke and smooth movement of the plug stem.
Irregular movement of the plug stem may indicate
internal defects.
NOTE: With graphite packing, irregular movement of
the plug stem is normal.
WARNING:
Keep hands, hair, clothing, etc. away from
all moving parts. Failure to do so can lead to serious
injury.
5.7
Check all accessories for firm seating.
5.8
If possible, close supply pressure and check the fail-
safe position.
5.9
Check stem boot for wear.
5.10
Check actuator for leaks. To do this, spray housing,
air connections and plug stem guide with leak spray
and check for any bubble formation.
5.11
Clean plug stem.
5.12
Check air filter, if present, and if necessary replace
insert.
Note:
For further information regarding service and
maintenance please contact your nearest FLOWSERVE
office.
DANGER:
On actuators with aluminium cases the
actuator springs must be renewed with original spare
parts every 10 years or after 50.000 operating hours
which ever occurs first.
Torque
Thread
PTFE
Grafoil
M20 x 1,5
1
3
M30 x 1,5
6
15
M38 x 1,5
15
35
M45 x 1,5
17
40
Table 1