beautypg.com

Flowserve Gas Barrier Control System User Manual

Page 3

background image

3

3.2 Use 316 stainless steel tubing to connect the Plant Nitrogen or Air supply to the Supply Inlet

port of the Control System. Minimum recommended tubing sizes are as follows unless

otherwise specified:

3/8 inch for mechanical seals (e.g. GF-200, GX-200, ML-200, GSL, GSD)

1/2 inch for segmented ring seals up to 127 mm (5.000 inch) seal size (e.g. Circpac MD)

3/4 inch for segmented ring seals up to 254 mm (10.000 inch) seal size

Contact Flowserve for all other seal types or the use of smaller tubing sizes

3.3 Use same size 316 stainless steel tubing as Step 3.2 to connect the Supply Outlet of the

Control System to the inlet of the Gas Seal.

3.4 Special Components

Maintenance Bypass Valve

Two ports are available for piping connection. Connect the port labeled “To Seal” to the inlet

of the Gas Seal as indicated in Step 3.3. The port labeled “Bypass” is connected to a

temporary gas source when Control System maintenance is required. This port is otherwise

not used. Set the bypass valve to the “Normal” position during normal operation.

Pressure or Flow Alarms

Connect alarm wiring to plant system per NEC 500 and plant specifications.

4 Operation

4.1 Turn on the Nitrogen or Air supply to the Control System.
4.2 For Plan 74 pressurized systems:

Adjust the Pressure Regulator until the Pressure Gage reads a predetermined pressure

above the pressure of the product being sealed (seal chamber pressure), taking into

consideration all phases of equipment operation. Consult the Flowserve Gas Seal assembly

drawing for the recommended barrier pressure over product pressure.

For Plan 72 unpressurized systems:

Adjust the Pressure Regulator until the Pressure Indicator reads a predetermined

pressure typically nominally above atmospheric or vapor/liquid collection system pressure.

Consult the Flowserve Seal Assembly Drawing for the recommended buffer pressure.

4.3 If a flow switch was supplied, and no set point was specified at time of order, it is factory set

at 5 SCFH rising. Please refer to the flow switch literature included in the manual for the

proper procedure to reset the switch set point.

4.4 If a pressure switch was supplied, and no set point was specified at time of order, it is

factory set at 1 bar (15 psig) falling. Please refer to the pressure switch literature included in

the manual for the proper procedure to reset the switch set point.

Note: For Plan 74 systems, the pressure switch set point should be 1.2 bar (17 psig)

above the pressure of the product being sealed (seal chamber pressure). Example: If seal

chamber pressure is 1.7 bar (25 psig), the pressure switch set point should be 2.9 bar

(42 psi) falling.

4.5 Check all connections to and from the control system for leakage with a leak detection

solution or soapy water.

4.6 Maintain the seal gas pressure even when the pump is not running.
4.7 The equipment is now ready for start up.