Fenix Watts V23 User Manual
Page 6

6
V23 Flush Receiver
 
 
Option: Floor Sensor 
NTC 10kOhms at 25°C 
 
1.
Presentation
 
- 
The V23 receiver is a Wall mounting receiver, specially designed to control electrical floor heating regulation in combination
or not with a wireless thermostat V22 type. 
- 
This couple (Thermostat Receiver) can also be managed by a Central V24 to have full control of your heating installation
from one point. 
- 
Possibility to connect a floor sensor directly on this unit (For regulation or floor limitation).
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
2.
Technical characteristics
Environment. (Temperatures) 
Operating : 
shipping et storage : 
 
0°C - 40°C 
-10°C to +50°C 
Power supply
230Vac 50Hz
Electrical protection
Class II - IP20 
Option: insulation clip for IP21 protection 
Pilot wire Input (French market)
6 orders Pilot Wire by phase (L)
Output 
Maximum Load 
Relay 16Amps 250VAC 
Up to 16A - 250Vac 50Hz (2 wires L,N) 
Radio Frequency & 
RF Receiving distance 
868MHz < 10mW (Bidirectional communication) 
Range of approximately 100m in open space. 
Range of approximately 30m in residential environment. 
Optional Floor Sensor
NTC 10kOhms at 25°C
Norms and homologation: 
 
Your thermostat has been designed in 
conformity with the following standards or 
other normative documents: 
EN 60730-1 : 2003 
EN 61000-6-1 : 2002 
EN 61000-6-3 : 2004 
EN 61000-4-2 : 2001 
 
EN300220-1/2 
EN301489-1/3 
 
R&TTE 1999/5/EC 
Low voltage 2006/95/CE 
EMC 2004/108/CE 
RF Configuration button 
Short press: Instantaneous RF transmission 
3sec press: Thermostat or Central RF init. 
5sec press: Slave receiver init. 
15sec press: Reset of the receiver. 
 
Status LED (RED/Green) 
Green: 
Fixed: 
RF configuration
Flash:
RF reception
OFF:
Standby
Blink:
RF Alarm
 
Red: 
Fixed: 
Floor Limitation
 
Red/Green (Orange) 
Fixed: Pilot wire information. 
 
Output LED (Red) 
Red: 
Heating demand
Blink:
Floor sensor error
GB