Installation

2-1

Section 2 : Installation


2.1 General

System

Reference Drawings: Pwr/Sig Entrance, 1 Driver Display ............. Drawing A-46755

System Layout, CH-836 .............................. Drawing A-47101
Display Splice Mounting Detail, CH-836H .. Drawing A-47102
Display Mounting, CH-836H ....................... Drawing A-47108
Installation Specifications, CH-836H........... Drawing A-47109
Component Locations, CH-836H ................ Drawing A-47112
Connector Plate, CH-836H ......................... Drawing A-47128
Color Code, 25-Pin J-Box ........................... Drawing A-47207

Refer to Drawing A-47101 for the general system layout.

The general procedure for installing the CH-836H display is as follows:

1. Select beam and footing recommendations from the table in Section 2.2.
2.
Dig the footing holes and install the beams and the footings.
3. Route power and signal cables to the display and control locations.
4. Mount the displays to the beams as described in Drawings A-47102, A-47108, and A-47109

and Section 2.3.

5. Route power and signal wires into the displays as described in Drawings A-46755, A-47112,

A-47128, and A-47207 and Section 2.4.


2.2

Beam and Footing Selection

Reference Drawings: Installation Specifications, CH-836H ........... Drawing A-47109

The table below contains recommendations for W-shape beams and footings to support the
display as shown in Drawing A-47109. The first column is wind velocity in miles per hour. The
distance in the second column is from the ground to the bottom of the display. The choice from
these columns depends upon the display location.

The beams listed below are beams which provide maximum wind load strength for the weight and
cost of the beams.

Wind Speed Height (ft)

Beam

Section

Footing Depth x

Diameter

70

10

W 10x19

7 ½ ftx3 ft

MPH

15

W 10x25

8 ¼ ftx3 ft

80

10

W 10x25

8 ½ ftx3 ft

MPH

15

W 10x29

9 ¼ ftx3 ft

90

10

W 14x26

9 ½ ftx3 ft

MPH

15

W 12x31

10 ½ ftx3 ft


The calculations for footing diameters and depths are based on the assumption that footings are in
undisturbed soils, not fill soils. Lateral bearing capacity of 300 psf per foot of depth in natural
grade was used to derive these figures.