Crydom DRA Series Contactors User Manual
Installation sheet, Dra series contactors, Din rail mount
Rev: 112213
3 Phase AC Contactors &
AC Motor Reversing Contactors
FEATURES
45 mm wide 3 phase & 62 mm wide motor reversing DIN rail mountable versions available
480 VAC Operating Voltage
5 VDC, 24 VDC, 48 VAC, 120 VAC & 230 VAC Input Control Voltage options available
Protective Forward/Reverse interlock built-in function for motor reversing
UL and IEC general use & Motor ratings available
LED Status indicator for Input Control Voltage
INSTALLATION INSTRUCTIONS
Please read all installation instructions before using DRA Series 3 Phase / Reversing Contactors.
fig. 1
Mounting/Dismounting contactor on DIN rail.
To install on DIN rail
To remove from
DIN rail
PART NUMBER NOMENCLATURE
DERATING CURVE
Required for valid part number
For options only and not required for valid part number
Lo
ad
C
ur
re
nt
(A
m
ps
)
0.0
1.0
2.0
3.0
4.0
5.0
0
10
20
30
40
50
60
Ambient Temperature (°C)
DRA3xxxx2
DRA3xxxx4
DRA Series Solid State Contactors offer the advantages of Crydom's proven state-of-the-art solid state AC
switching technology in a ready-to-use contactor which requires no additional heat sinking. DRA Series
Contactors include a protective Forward/Reverse interlock for motor reversing and are ideal for applications
up to 2 Horse Power. For complete specifications, see DRA Series AC 3 Phase Contactors & DRA AC Motor
Reversing Contactors datasheets at www.crydom.com.
Install the contactor on the DIN rail as shown in fig. 1. Vertical
mounting operation is recommended.
If multiple units are installed be sure to follow derating curve (fig. 2).
DRA Series Contactors
(A)
(B)
(C)
(A,B)
Unless otherwise noted, all
ratings are at 0 mm air gap for
adjacent similar parts.
Resistive Load Current rating
for AC Control is 3.4 A @ 0 mm
air gap. For maximum ratings
use 45 mm air gap.
AC-53a rating for DRA3Pxxx2
(A, B & C suffix) is 0.55 KW @
480 VAC.
(D)
AC-53a rating for DRA3Pxxx2
(A, B & C suffix) is 0.37 KW @
480 VAC.
fig. 2
Derating Curve for 3 Phase & Motor Reversing contactor.
Temp.
40°C
1 HP (0.75 KW)
(C)
(D)
60°C
¾ HP (0.55 KW)
2 HP (0.75 KW)
1 HP (0.37 KW)
DRA3Pxxx2
DRA3Pxxx4
1 HP (0.75 KW)
¾ HP (0.55 KW)
2 HP (1.5 KW)
1 HP (0.75 KW)
DRA3Rxxx2
DRA3Rxxx4
Wire the contactor to the input control side following the
corresponding wiring diagram (fig. 3 or fig. 4). AWG #24 minimum,
AWG #12 maximum (0.2-3.3 mm
2
), choose wire gauge according to
load current. Maximum recommended terminal screw torque input
4.3 in-lbs (0.5 Nm).
Wire the contactor to the AC Line side (L1, L2 & L3) and to the Load
side (T1, T2 & T3). AWG #24 minimum, AWG #10 maximum (0.3-5.3
mm
2
), choose wire gauge according to load current. Maximum
recommended terminal screw torque output 12 in-lbs (1.37 Nm).
Series
Operating Voltage
40: 48-415 VAC
(Only for 3R)
48: 48-510 VAC
Rated Load Current
2: 2.4 Amp/
1HP @ 480 VAC
4: 4.2 Amp/
2HP @ 480 VAC
Control Voltage
D: 4-6 VDC
E: 18-28 VDC
A: 200-265 VAC
B: 90-140 VAC
C: 36-60 VAC
Function
3P: 3 Phase
3R: Reversible
Switching Type (Only for 3P)
Blank: Zero Voltage Turn-On
R: Instantaneous Turn-On
4
48
D
DRA
3P
R
Controlled Legs
(Only for 3P)
Blank: 3 Legs
2: 2 Legs
2
Installation Sheet
DIN Rail Mount
Do not forget to visit us at:
www.crydom.com
Copyright © 2014 Custom Sensors & Technologies. Specifications subject to change without notice.