Appendix, Technical data, Approvals – BECKHOFF C9900-P208 User Manual
Page 20
Appendix
18
C9900-P208 / C9900-P209
Appendix
Technical data
Electrical data
Input voltage:
22-30V DC/ 15A
Power output: 250W
(max.)
Output voltages: see
section
Electrical data
Dimensions
Dimensions (W x H x D):
97.0 x 44.0 x 204.9 mm
Weight: 0.85
kg
Do not use the power
supply unit in areas of
explosive hazard
The power supply unit must not be used where there is a risk of
explosion.
The following conditions must be observed during operation:
Environmental conditions
Ambient temperature:
0 to 55°C
Atmospheric humidity:
Maximum 95%, non-condensing
Shock resistance
Sinusoidal vibration
(EN 60068-2-6):
10 to 58 Hz:
0.035 mm
58 to 500 Hz: 0.5 G (~ 5 m/ s
2
)
Impact
(EN 60068-2-27/ -29):
5 G (~ 50 m/ s²), duration: 30 ms
EMC compatibility
Resistance to interference: according to EN 61000-6-2
Emission of interference: according to EN 61000-6-4
Transport and storage
The same values for atmospheric humidity and shock resistance are to be
observed during transport and storage as in operation. The shock
resistance during transport can be improved by appropriate packaging of
the power supply unit. The ambient temperature during storage and
transport must be between -20°C and +65°C.
Approvals
FCC: Federal Communications Commission
Radio Frequency Interference Statement
FCC Approval for USA
This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, may
cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in
which case the user will be required to correct the interference at his own
expense.
FCC: Canadian Notice
FCC Approval for Canada
This equipment does not exceed the Class A limits for radiated emissions
as described in the Radio Interference Regulations of the Canadian
Department of Communications.