Notes about operation in potentially explosive areas

CX50x0 units in potentially explosive areas

5

2 Notes about operation in potentially explosive

areas

2.1 Special conditions

WARNING

Observe the special conditions for the intended use of Beckhoff fieldbus
components in potentially explosive areas (directive 94/9/EU)!

 The certified components are to be installed in a suitable housing that

guarantees a protection class of at least IP54 in accordance with EN 60529!
The environmental conditions during use are thereby to be taken into account!

 If the temperatures during rated operation are higher than 70 °C at the feed-in

points of cables, lines or pipes, or higher than 80°C at the wire branching
points, then cables must be selected whose temperature data correspond to
the actual measured temperature values!

 Observe

the permissible ambient temperature range of 0 - 55°C for the use of

Beckhoff fieldbus components in potentially explosive areas!

 Measures must be taken to protect against the rated operating voltage being

exceeded by more than 40% due to short-term interference voltages!

 The individual terminals may only be unplugged or removed from the Bus

Terminal system if the supply voltage has been switched off or if a non-
explosive atmosphere is ensured!

 The connections of the certified components may only be connected or

disconnected if the supply voltage has been switched off or if a non-explosive
atmosphere is ensured!

 The fuses of the KL92xx power feed terminals may only be exchanged if the

supply voltage has been switched off or if a non-explosive atmosphere is
ensured!

 Address selectors and ID switches may only be adjusted if the supply voltage

has been switched off or if a non-explosive atmosphere is ensured!

 The optional audio interface CX50x0-N020 may not be used in EX

environment!

 The certified components must be used the modification CX1900-0105. The

modification involves the relocation of the type plate and a mounting bracket to
ensure the fixing of the cables from the USB ports. Both modifications are
factory-provided.

The fundamental health and safety requirements are fulfilled by compliance with the following standards:

EN 60079-0:2012 + A11:2013

EN 60079-15:2010

This manual is related to the following products: