Installation – Avalon Firestyles AGP User Manual
Page 13

Installation
(For Qualified Installers Only)
13
© Travis Industries
4141230
100-01270
Mobile Home Requirements
Outside air is required (used for combustion) - see the directions below.
The heater must be bolted to the floor (Some states do not require this; check with your local building
department).
The heater must be grounded to the steel chassis of the mobile home (Some states do not require this;
check with your local building department).
DO NOT INSTALL IN SLEEPING ROOM.
CAUTION:
THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR, WALL, AND
CEILING/ROOF MUST BE MAINTAINED.
Outside Air (Used for Combustion
Use Part #99200136)
Travis Industries strongly recommends outside air for all installations, especially for those with
relatively air-tight homes or with vents that do not include vertical rise.
Must not be drawn from an enclosed space (garage, unventilated crawl space).
Must not be over 48” (1220mm) long
Must be made with 1-¾” (45mm) diameter or larger metal or aluminum duct with a metal screen
attached to the end to keep out rodents (P.V.C. or other combustible materials may not be used).
We recommend the Travis Industries Outside Air Kit (part # 99200136).
Must not terminate above or within 1' (305mm) of the chimney termination.
Must have a rain cap or down-turned elbow to prevent water from entering.
Must be located so that it will not become plugged by snow or other material.