Status display / error codes – ZENNER MULTIDATA WR3 User Manual

Page 9

background image

9

Symbol

Status

Maßnahme

Flow existent

-

Attention!

Check system / device for errors

Data transmission

-

Emergency operation

Exchange device

External power supply

-

Status display / Error codes

The symbols in the table below show the meter’s operational status. The status messages only appear
in the main display (energy)! The temporary display of the warning triangle can be caused by special
operating states and does not always mean that the device is malfunctioning. However, should the symbol
be displayed over a longer period of time you should contact the service company.

Error codes show faults detected by multidata. If more than one error appears, the sum of the error
codes is displayed: Error 1005 = error 1000 and error 5.
.

Code

Error

Event

1

Short-circuit return sensor

Check sensors, replace if needed

2

Interruption return sensor

Check sensors, replace if needed

3

Short-circuit supply sensor

Check sensors, replace if needed

4

Interruption supply sensor

Check sensors, replace if needed

5

Hardware error

Exchange device

6

Battery empty or wrong temp. sensor

Check device / sensor

7

Temperatures out of measuring range

Correction heating system

100

Emergency operation

Exchange device

1000

Battery life time exceeded

Exchange device

2000

Initial verification expired

Exchange device

> 8000

Internal hardware error

Exchange device