4. Addressing
The ADDRESS of the inputCUE-W can be set in the range 0 to 207. Default ADDRESS is 1.
The BUTTON_ID transmitted by the inputCUE-W is the LINK number used in the programming for
button identification. The BUTTON_LED_ID is LED identification for ButtonLed… commands. Both
values depend on the Input (Output) Number and on the ADDRESS too. BUTTON_ID is calculated
according to the formulas described below.
BUTTON_ ID
=
(32 * ADDRESS) + Input Number
BUTTON_LED_ID
=
(32 * ADDRESS) + Output Number
The ADDRESS of the inputCUE-W is binary coded by DIP switch.
Switch view
Switch nr.
Function
SW1
ADDRESS bit 0
SW2
ADDRESS bit 1
SW3
ADDRESS bit 2
SW4
ADDRESS bit 3
SW5
ADDRESS bit 4
SW6
ADDRESS bit 5
SW7
ADDRESS bit 6
SW8
ADDRESS bit 7
ADDRESS
SW1
SW2
SW3
SW4
SW5
SW6
SW7
SW8
0
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
1
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
3
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
4
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
...
207
ON
ON
ON
ON
OFF
OFF
ON
ON
In the table below Button ID range for some addresses is shown.
ADDRESS
BUTTON_ID range = BUTTON_LED_ID range
0
1
8
1
33
40
2
65
72
…
…
…
207
6625
6632
User Manual inputCUE-W