4. Addressing
Each unit connected to the CUEwire bus must have its unique address. These addresses for
touchpanels and keyboards are set in configuration and are called „panel addresses“. The same type
of address is set for each sensorCUE-W. Its value must be unique for each unit on the CUEwire bus.
The ADDRESS of the sensorCUE-W is binary coded by DIP switch located on the rear panel.
The ADDRESS can be set in the range 1 to 127. Default ADDRESS is 15.
Switch view
Switch nr.
Function
Address bit’s weight
SW1
ADDRESS bit 0
1
SW2
ADDRESS bit 1
2
SW3
ADDRESS bit 2
4
SW4
ADDRESS bit 3
8
SW5
ADDRESS bit 4
16
SW6
ADDRESS bit 5
32
SW7
ADDRESS bit 6
64
SW8
Not used
Not used
ADDRESS
SW1
SW2
SW3
SW4
SW5
SW6
SW7
1
ON OFF OFF OFF OFF OFF OFF
2
OFF ON OFF OFF OFF OFF OFF
3
ON ON OFF OFF OFF OFF OFF
4
OFF OFF ON OFF OFF OFF OFF
5
ON OFF ON OFF OFF OFF OFF
6
OFF ON ON OFF OFF OFF OFF
7
ON ON ON OFF OFF OFF OFF
8
OFF OFF OFF ON OFF OFF OFF
9
ON OFF OFF ON OFF OFF OFF
…
… … … … … … …
15
ON ON ON ON OFF OFF OFF
…
… … … … … … …
126
OFF ON ON ON ON ON ON
127
ON ON ON ON ON ON ON
User Manual sensorCUE-W
www.cuesystem.com
Page 7 of 14