Configuration of sntl300-p via rs485 – Computronic Controls Sentinel 300P User Manual
Page 20

SNTL300P-PCSUITE installation & operation
ci0042 p20/22 issue 5 2015-04-22
Configuration of SNTL300-P via RS485
In order for customers to transmit their own remote profiles to the SNTL300P, the following protocol must be
used:
Packet must be sent in MODBUS RTU format.
Use the ‘Set multiple holding registers’ command (0x10)
Slave address must equal that of the charger. (Default of 100)
Register start address = 64
Number of points = 17
Register
SNTL300P Function
Scaling
40064
Float voltage
Voltage X 10
40065
Boost voltage
Voltage X 10
40066
Boost initiate voltage
Voltage X 10
40067
Boost period
Minutes
40068
Low alarm voltage
Voltage X 10
40069
High alarm voltage
Voltage X 10
40070
Number of cells
Cells X 1
40071-40080
Profile name
2 ASCII characters per register