beautypg.com

Dimensions – ABUS Technologies USI Universal Smart Isolator User Manual

Page 5

background image

ABUS TECHNOLOGIES INC.

5

USI

2.2 Technical Parameters

Accuracy:

±0.2% FS ± 1 for resistance mVDC VDC and mADC

±0.5% FS ± 1 for thermocouple input.

Output:

0...5 V, 0...10 V, 0.5...4.5 V, 4...20 mA

(Customized On

request)

Power Supply:

100~240V AC (50/60Hz, 100~240V AC)

22~26V AC (50/60Hz, 24V AC)

22~26V DC (24V DC).

Isolated Resistance:

10MΩ or more between input and case at DC 550V

10MΩ or more between output and case at DC 550V.

Dielectric Strength:

1000V AC for 1 minute between input terminal and case

1500V AC for 1 minute between output terminal and case.

Load Resistance:

DC mA Output

PID O/P:

500Ω

Transmission O/P: 220Ω

VDC Output

Max. Load Current: 20mA

Input Impedance:

DC mA Current Input: 200Ω

DC V Voltage Input: 500KΩ

Thermocouple Input: 4.7 KΩ

3. DIMENSIONS