Dimensions – ABUS Technologies USI Universal Smart Isolator User Manual
Page 5

ABUS TECHNOLOGIES INC.
5
USI
2.2 Technical Parameters
Accuracy:
±0.2% FS ± 1 for resistance mVDC VDC and mADC
±0.5% FS ± 1 for thermocouple input.
Output:
0...5 V, 0...10 V, 0.5...4.5 V, 4...20 mA
(Customized On
request)
Power Supply:
100~240V AC (50/60Hz, 100~240V AC)
22~26V AC (50/60Hz, 24V AC)
22~26V DC (24V DC).
Isolated Resistance:
10MΩ or more between input and case at DC 550V
10MΩ or more between output and case at DC 550V.
Dielectric Strength:
1000V AC for 1 minute between input terminal and case
1500V AC for 1 minute between output terminal and case.
Load Resistance:
DC mA Output
PID O/P:
500Ω
Transmission O/P: 220Ω
VDC Output
Max. Load Current: 20mA
Input Impedance:
DC mA Current Input: 200Ω
DC V Voltage Input: 500KΩ
Thermocouple Input: 4.7 KΩ
3. DIMENSIONS