7

DFT

6. INSTALLATION


6.1 Mounting

The DFT Series should be mounted in a clean, dry location free from excess

vibration. The transmitter can be mounted in any orientation and should be attached by

using the 4 holes provided on the housing.

6.2 Pressure Connections

Two push on pressure connections are located on the front of the unit, labeled

“High” and “Low”. For best results, connect 1/8” I.D. push on tubing to the pressure

connections. For differential pressure measurement, the higher pressure should be

connected to the “High” pressure port. For positive pressure, the “Low” pressure port

should be left vented to atmospheric pressure. For negative pressure measurement, the

“High” pressure port should be vented to atmospheric pressure.


7. MAINTENANCE


Calibration

The DFT Series is factory calibrated and should not require calibration out of the

box. Periodically, it may be necessary to recalibrate the gauge to maintain the accuracy of

the product. To “zero” the gauge, remove the pressure connections from both pressure

ports and adjust the zero potentiometer until the output is 4 mA. To “span” the gauge, apply

the full scale pressure to the High pressure port and adjust the span potentiometer until the

output is 20 mA. To properly calibrate the product, it is necessary to have an accurate

pressure standard. If you do not have one available or would like calibration traceable to

NIST, please contact ABUS Technologies Inc.