beautypg.com

TFC Group Trealux 610 User Manual

Page 4

background image

4

GB

3.

Technical Data

Dimensions H x W x D mm

45 x 17,5 x 60

Distributor section mm

46 x 18,5

Connection

see unit imprint

Switching capacity AC

ohmic load (VDE, IEC) cos phi 1

16 A/230 V

inductive load cos phi 0,6

10 A/230 V

incandescent lamp load

2300 W

fluorescent lamp in DUO circuit

20 x 2 x 58 W

fluorescent lamp, parallel-compensated

20 x 58 W

fluorescent lamp, series-compensated

40 x 58 W

electronic ballast

5 x 20 W

conventional ballast

1500 W

Switching contact

N/O contact

Ambient temperature

–10° C … +55° C

Protection class/type

II/IP 20

Adjustment range

0.5 … 99.5 minutes

Glow lamp load

max. 50 x 1 mA

ON period

100% on-load factor

Hand switch

yes

Resettable

immediately

Attachment

captive +/– screws

Connection type

3/4 wire connection

Diagnosis functions

yes

Caretaker function = 1 hour

press approx. 3 seconds

Options/prewarning

yes