Test Products International 605 User Manual
Page 3
A. INTRODUCTION
1.
Congratulations: Thank you for purchasing TPI products. The 605 is
easy to use and built to last. Please remember to complete and return
your product warranty registration card.
2.
Product Description: The 605 vacuum gauge measures vacuum in
Micorns for accurate evacuation of refrigeration systems. Please follow
manufactures recommendations on all HVAC equipment.
B. SAFETY CONSIDERATIONS
1.
Wear safety gogles.
2.
Make sure system is at atmospheric pressure before attaching vacuum
gauge.
3.
Check all connections making sure they are secure with no leaks.
4. Observe all mnufacturers recommendations.
C. General Specifications
Sensor Type
Thermistor
Connector Type
Standard 1/4” Male Flare Fitting
Range
12,000 - 0 Microns
Units of Measure
Microns, PSI, InHg, mBar, Pascals
Torr, mTorr
Over Pressure
500 PSI
Operating Temperature
32° to 120°F (0° to 150°C)
Power Supply
9 Volt Alkaline
D. Accuracy
Measurement
Range
Resolution
Accuracy
0 - 50
1 Micron
Microns
151 - 400
5 Microns
401 - 500
10 Microns
+/- 10% of reading,
501 - 1000
20 Microns
+ 10 digits
1001 - 2000
50 Microns
2001 - 12000
500 Microns
E. MEASUREMENT TECHNIQUES
1.
Attach the 605 to the system to be evacuated.
2.
Select the desired unit of measure.
3.
Start the vacuum pump and proceed to evacuate the system.
Please note: The 605 will not start to display a reading until 12,000 microns
(-29.4 inHg) is reached.
F. ACCESSORIES
Item #
Description
A009A ....................................9 Volt Alkaline Battery
A100 ......................................Soft Carrying Pouch
Microns
InHg below ATM
12000
29.47
10000
29.53
8000
29.69
4000
29.76
2000
29.84
1000
29.88
500
29.90
300
29.91
200
29.91
150
29.92
100
29.92
50
29.92
0
29.92