Dodge Engineering & Controls, Inc.

Toll Free (877) 334-2875 Fax: (978) 244-1422

Installation

EN221 and EN310 Non-Spring Return Electronic Actuators

Sizing Actuators for Damper Applications


The number of actuators required depends on several factors. To determine the quantity of actuators required for
the installation:

• Obtain damper torque ratings (ft-lb/ft

2

or Nm/m

2

) from the damper manufacturer.

• Determine the area of the damper.
• Calculate the total torque required to move the damper:

Total Torque = Torque Rating x Damper Area

Select the total quantity of actuators, required:

Number of Actuators =

Total Damper Torque required

SF

(see note

below)

Actuator Torque

(refer to

specifications)

x

NOTE: When calculating the number of actuators required, a safety factor (SF) should be included for

unaccountable variables such as slight misalignments, aging of the damper, etc. A suggested
safety factor is 0.80 (or 80% of the rated torque).

Mechanical coupling of the actuator is allowed if:
− The same type of actuator is used.
− The power trunk can handle added components.
− The same control input goes to both actuators (parallel wiring).