beautypg.com

Shut down, Tank to tank transfer, Push / pull recovery – REFCO Powermax User Manual

Page 5

background image

PUSH / PULL RECOVERY

(LIQUID RECOVERY FOR 20 LBS. OR MORE)

SET-UP
1. CONNECT HOSES AS SHOWN BELOW.
2. CLOSE INLET VALVE (V1).
3. TURN CONTROL VALVE (V2) TO RECOVER POSTION.
4. OPEN DISCHARGE VALVE (V3).
5. OPEN LIQUID & VAPOR VALVES ON THE RECOVERY TANK.

OPERATION
1. TURN POWER ON AND PRESS START BUTTON.
2. SLOWLY OPEN INLET VALVE (V1).
3. ONCE ALL LIQUID HAS BEEN RECOVERED, GO TO VAPOR

RECOVERY (FIG 2).

SHUT DOWN
1. CLOSE INLET VALVE (V1) ONCE DESIRED VACUUM IS ACHEIVED.
2. CLOSE LIQUID VALVE ON RECOVERY TANK.
3. CLOSE DISCHARGE VALVE (V3).
4. TURN POWER SWITCH OFF.

4

TANK TO TANK TRANSFER

SET-UP
1. CONNECT HOSES AS SHOWN BELOW.
2. CLOSE INLET VALVE (V1).
3. TURN CONTROL VALVE (V2) TO RECOVER POSTION.
4. OPEN DISCHARGE VALVE (V3).
5. OPEN LIQUID VALVE ON THE RECOVERY TANK (A).
6. OPEN LIQUID VALVE ON THE RECOVERY TANK (B).

OPERATION
1. TURN POWER ON AND PRESS START BUTTON.
2. SLOWLY OPEN INLET VALVE (V1).

SHUT DOWN
1. CLOSE INLET VALVE (V1) ONCE DESIRED VACUUM IS ACHEIVED.
2. CLOSE BOTH LIQUID VALVES ON EACH RECOVERY TANK.
3. CLOSE DISCHARGE VALVE (V3).
4. TURN POWER SWITCH OFF.

(A) FULL TANK (B) EMPTY TANK 5