Elevation view of indicator post and valve, Field adjustment instructions – NIBCO NIP-1AJ Indicator User Manual
Page 2
A H E A D O F T H E F L O W
®
www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227
TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
2
ELEVATION VIEW OF INDICATOR POST AND VALVE
17-4 Kennedy Valve/Indicator Posts
1
1
/
4
" Sq.
1" Sq. Stem
9"
36
3
/
4
"
5
1
/
8
"
30"
6" Dia.
12" Dia.
Trench
Depth
Ground Line
Standpipe
(painted red)
Standpipe
(painted black)
Top Section
max. = 10"
min. = 7"
INDICATOR POST STYLE 2945
FIXED LENGTH UL/FM
DIMENSIONS AND INSTRUCTIONS
KENNEDY VALVE
Available in Sizes F G H
See Page 6 for Dimensions
FIELD ADJUSTMENT
INSTRUCTIONS
1. Remove the top section from the top of the
Indicator Post assembly.
2. Cut the required length off the bottom of the
Standpipe for the Ground Line to match up
with Standpipe Ground Line mark.
3. Cut the 1" Sq. Stem at a distance of 9"
above the top of the Standpipe.
4. Set the “OPEN” and “SHUT” targets for the
appropriate valve size.
5. Reattach the Top Section to the top of the
Indicator Post assembly.
Updated 05/02/2012
Fig. 2
Fig. 3