READ AND FOLLOW ALL SAFETY INSTRUCTIONS!
2.1 Disconnect Power
Make sure the generator is off, the external power cord is unplugged, and the
inverter, if any, is shut off.
2.2 Mounting Location
The TS-50 mounting location may be on any interior surface where the unit will be
out of direct weather. The chosen location must be accessible after installation is
complete to facilitate future servicing. If possible, mount the TS-50 near the power
cord entry or the location of the generator output. Typical locations include under
counter cabinets, below closet compartments, inside the bed pedestal or cabinets,
overhead cabinets, under-floor storage compartments accessed from the vehicle
exterior, etc.
2.3 Electrical Preparation
Use knockouts 12, 5, and 6 when installing the TS-50. Do not use knockouts 3, 4,
7, and 8 when preparing the TS-50 for installation.
2.4 Mounting
Mount the TS-50 with screws through holes provided in bottom corners of the can.
The unit should be screwed to a solid surface firmly enough to hold its weight
during vehicle operation.
2.5 Electrical Connections
A. Attach an 8 gauge chassis ground wire to the transfer switch ground bar.
A direct access hole to the ground bar is provided through the enclosure for
convenience.
B. Determine proper connections of wire conductors to electrical terminals.
On 120 VAC wiring the ground wire is bare or green, the neutral wire is
white, and the hot wire is black. On 240 VAC wiring there are two hot wires;
one is black, and the other is red.
C. Strip the outer jacket from all of the incoming cables. Strip insulation from
all ends of the copper conductors. Insert cables through clamps in openings.
Do not tighten cable clamps at this time.