beautypg.com

2 internal electronic circuitry, Isa-ral-m, isa-rah-m enmet corporation 3, 110 vac power supply outside of control unit – ENMET ISA-RAL-M User Manual

Page 7: N.c.= normally closed n.o.= normally open

background image

ISA-RAL-M, ISA-RAH-M

ENMET Corporation

3

3.2 Internal Electronic Circuitry

Figure 5 shows the circuit board and terminal blocks housed inside the hinged oiltight control unit. Specific relays and
adjustments are defined:

Internal Relay Contacts

Relays can be used to activate an external remote alarm signal when a
hazardous CO level is detected, or when the ac or dc power is interrupted.
These are double-pole relays with terminals normally open, normally closed
and common (see Figure 3 for relay contact hook-up). There is one relay for
each alarm level.

Potentiometers:

The unit has five potentiometers. Only 3 are used by the customer. These vary
critical circuit resistances and are essential to calibration procedures. These
potentiometers are described below.

Meter Adjust

To adjust and set the meter for appropriate gas response during calibration.

Low Level Set

To adjust the trip level of the amber gas alarm light and the audio alarm.

High Level Set

To adjust the trip level of the red gas alarm light and the audio alarm.

Figure 3: Utilizing the Relay Contacts

Figure 5: Internal Electronic Circuitry

Normally
Closed
Contact

Common
Contact

110 Vac

Power supply Outside

of Control Unit

Manual On/Off
Switch

Horn

White

Black

Non-Latching Relay contacts:
Identified below is the non-powered
(power to unit is off), alarm positions of
the non-latching relay contacts.

Terminal Block 2 see Figure 5
Relay 1

High Alarm

Relay 2

Low Alarm

N

OTE

:

N.C.= normally closed
N.O.= normally open

Suggested wiring configuration for Utilizing Relay Contacts
(manual on/off switch is suggested; user supplied component)

Low Level Set
Potentiometer

High Level Set
Potentiometer

Meter Adjust
Potentiometer

110 / 115

OR

210 / 230*
*See Section 4.0

12 VDC

INPUT

Internal Relay
Contacts

Red Lamp

----

Green Lamp

Amber Lamp

Purge

GND

Meter+

Meter–

TB3

TB2

TB1

Relay 1

GND

GND

Battery

Backup

GND

GND

Signal

Heater

Sensor

COM

.

N.C.

COM.

N.O.

N.O.

N.C.

Relay 2

TB4

GND

110 VAC

110 VAC

RV34

RV32

RV38

RV35

TP1

RV33

K1

K2

Jumper Holder

Jumper 1

Jumper 2

Jumper 5

Jumper 4

Jumper 3

TP2