Commissioning
F
AN
O
PERATION
• Check that pulleys are correctly aligned.
• Check the belt tension is correct. Nominally 15
– 20mm depression.
• Check bearings are tight on shaft
• Set the fan running and check.
• Check that the air is being evenly distributed
through the ductwork.
• Make adjustments, as required, to any manual
air dampers that may be fitted.
• Fan Motor Current. Check the motor
operating current is not greater the rating plate
value.
o
For systems with high statics and
non standard drive check motor
current. Where required, review
pulley requirements relative to the
system static. Where variable pitch
pulleys are fitted adjust accordingly.
o
For systems with minimal static eg
straight dropper and plenums,
check motor current. A smaller
motor pulley to standard may be
required.
C
ONTROLS
Check all control functions are working
C
USTOMER HAND
O
VER
Instruct the customer in the use of the product.
• Controls
• Bleed
off
• Venting the air via the side of the premises the wind is not blowing from.
• Maintenance
Requirements
Hand over of the customer’s operational manual.