Prohibit a a, Aprohibit a – Delta Electronics Timer/Counter/Tachometer CTA User Manual
Page 2
7.
Counter Function
Counter functions include 1-stage counting, 2-stage counting, batch counting, total counting and dual counting.
1-stage Only 1 SV is allowed. See “output modes of counter”.
2-stage 2 SVs, 2 PVs are allowed. See “output modes of counter”.
Batch
Apart from the counting of PV and SV, when PV=SV, the batch counting adds 1 and clear PV as 0 for
recounting till the batch counting equals batch SV.
Total
Total counting adds up all the counting values till they reach SV for output.
Dual
CP1 and CP2 can be independent counters, but the counting speed can only reach 5kHz. CP1 and CP2
can execute addition
or subtraction
.
Counting up
Counting down
Input modes of counter
Counting up
Counting down
Command
Individual
Quadrature
Prohibit
A
A
0
1
2
3
4
H
L
H
L
0
CP1
CP2
Present
Value
CP1: Counter input CP2: Counter input prohibited
Note: has to be larger than width of min. Input signal
A
Prohibit
A
A
0
1
2
3
4
5
H
L
H
L
0
CP1
CP2
Present
Value
CP1: Counter input prohibited CP2: Counter input
Note: has to be larger than width of min. Input signal
A
Prohibit
A
A
n
n-2
n-1
n-4
n-3
H
L
CP1
CP2
Present
Value
0
H
L
CP1: Counter input CP2: Counter input prohibited
Note: has to be larger than width of min. Input signal
A
A
Prohibit
A
n
n-1
n-2
n-3
n-4
n-5
H
L
H
L
CP1
CP2
0
Present
Value
CP1: Counter input prohibited CP2: Counter input
Note: has to be larger than width of min. Input signal
A
Command counting up/down
UD_A
Individual counting up/down
UD_B
Quadrature input
UD_C
B
B
B
B
0
1
1
2
2
3
H
L
CP1
CP2
Present
Value
0
Note: has to be larger than width of 1/2 min. input signal.
B
H
L
0
Output modes of counter
:
The output of SV can be 1-stage or 2-stage. When the output is set as 1-stage, Output 2 will be the same as the Output 1. The
output modes include: F, N, C, R, K, P, Q, A, S, T, D
F When PV reaches SV, output is enabled but counting continues. Recounting starts after reset signal is over.
Output 2 remains.
N When PV reaches SV, output is enabled but counting stops. Recounting starts after reset signal is over. Output 2
remains.
C When PV reaches SV, recounting executes automatically. Output 2 is pulse output. Output 1 remains till Output 2
is over.
R When PV reaches SV, counting stops till Output 2 (pulse) is over for recounting. Output 1 remains till Output 2 is
over.
K When PV reaches SV, output is enabled but counting continues. Recounting starts after reset signal is over.
P When PV reaches SV, output is enabled and recounting is automatically executed. But display of counting
remains till Output 2 (pulse) is over.
Q When PV reaches SV, output is enabled but the counting continues. Recounting starts after Output 2 (pulse) is
over.
A When PV reaches SV, output is enabled but the counting stops. Recounting starts and Output 2 (pulse) executes
after reset signal is over.
S When PV ≥ SV1, Output 1 is enabled. When PV ≥ SV2, Output 2 is enabled
T When PV ≤ SV1, Output 1 is enabled. When PV ≥ SV2, Output 2 is enabled.
D When SV=PV, output is enabled but counting continues. Addition and subtraction modes are valid.
The time of Output 1 and Output 2 (pulse) can be setup separately, ranging from 0.01 to 99.99 secs. Recounting refers to counting up or
addition/subtraction counting starting from 0 and counting down starting from SV. The counting range: -99999~999999. The counting
will restart from 0 if the counting exceeds the range.
999999
RESET
SV2
SV1
OUT2
OUT1
0
T
T
T
T
T T T
T
T
T
RESET
999999
SV2
SV1
0
OUT2
OUT1
T
T
RESET
999999
SV2
0
OUT2
OUT1
SV1
RESET
999999
SV2
SV1
0
OUT2
OUT1
T
T
T
T
T
T
T
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Input mode
Up
Down
Up/Down A, B, C
F
N
C
R
Output
mode
setting
RESET
999999
SV1
SV2
0
OUT2
OUT1
RESET
999999
SV2
SV1
0
OUT2
OUT1
RESET
999999
SV2
SV1
0
OUT2
OUT1
RESET
999999
SV1
SV2
0
OUT2
OUT1
Output
mode
setting
Input mode
Up
Down
Up/Down A, B, C
K
P
Q
A
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
RESET
999999
SV2
SV1
0
OUT2
OUT1
RESET
999999
SV2
SV1
0
OUT2
OUT1
RESET
999999
SV1
SV2
0
OUT2
OUT1
Output
mode
setting
Input mode
Up/Down A, B, C
S
T
D
Save the data before power off
: When
is set, the current PV will be saved. When
is displayed, the
PV will be cleared.
Pre-scale function
: When conducting unit conversion, PV = PV x PreScale value, ranging from 0.001 to 99.999.
8.
Tachometer Function
Measuring Rotation speed: Measuring pulse width and determining current frequency
Output methods: Lo-Lo, Lo-Hi, Hi-Lo, Hi-Hi
OUT2 set value
Measurement value
OUT1 set value
OUT1
OUT2
OUT1 set value : OUT1 ON
Measurement value
OUT2 set value : OUT2 ON
(LO-LO)
OUT2 set value
Measurement value
OUT1 set value
OUT1
OUT2
Measurement value
OUT1 set value : OUT1 ON
Measurement value
OUT2 set value : OUT2 ON
(LO-HI)
OUT2 set value
Measurement value
OUT1 set value
OUT1
OUT2
(HI-LO)
Measurement value
OUT1 set value : OUT1 ON
Measurement value
OUT2 set value : OUT2 ON
OUT2 set value
Measurement value
OUT1 set value
OUT1
OUT2
(HI-HI)
Measurement value
OUT1 set value : OUT1 ON
Measurement value
OUT2 set value : OUT2 ON
Delay time after switching on the power
: The tachometer will start to run when the set delay time is due after the
power is switched on. (Range of delay time: 0.1~99.9 secs.)
Setup average value of input filter
: Range for obtaining average (n = 0 ~ 3). This parameter obtains the average of 2
n
input data for more stable output value.
9.
Timer + Counter Mixed Function
In Timer + Counter function, SV1, PV1 and Output 1 are for Timer; SV2, PV2 and Output2 are for Counter. DIP switch is
disabled. All timer and counter functions remain except
․
RCY2, SCON, STON, STOFF in output mode of Timer function
․
Command up/down, Individual up/down, quadrature counting in input mode, S, T, D in output mode of Counter function
Only 1-stage counting in Counter function is available.
10.
Easy DIP Switch Setup
Users can use DIP switch to setup parameters. When DIP is switched to ON, the corresponding parameters can only be
read, not changed.
SW
Counter
Timer
Tachometer
8
Reset pulse width
ON: 1ms, OFF: 20ms
Reset pulse width
ON: 1ms, OFF: 20ms
Reset pulse width
ON: 1ms, OFF: 20ms
7
Input type
ON: PNP OFF: NPN
Unit of Timer
See Table 1
Input type
ON: PNP OFF: NPN
6
N/A Unit
of
Timer
See Table 1
N/A
5
Counting speed
ON: 10K CPS OFF: 30 CPS
Unit of Timer
See Table 1
Counting speed
ON: 10KHz OFF: 30Hz
4
Output mode of counter
See Table 2
Output mode of Timer
See Table 2
Output mode of Tachometer
See Table 2
3
Output mode of counter
See Table 2
Output mode of Timer
See Table 2
Output mode of Tachometer
See Table 2
2
Input mode of counter
ON: counting down OFF: counting up
Time counting up/down
ON: down OFF: up
N/A
1
ON: Enable DIP
OFF: Disable DIP
ON: Enable DIP
OFF: Disable DIP
ON: Enable DIP
OFF: Disable DIP
SW5 SW6 SW7
Displayed unit
OFF OFF OFF 0.01
sec
ON OFF OFF 0.1
sec
OFF ON OFF 1
sec
Output Mode Configuration
ON
ON
OFF min, 0.01 sec
SW3 SW4
Counter
Timer
Tachometer
OFF
OFF
ON
min, 0.1 sec
OFF
OFF
F
Signal ON Delay 1
Lo-Lo
ON OFF ON 0.1
min
ON
OFF
N
Signal ON Delay 2
Lo-Hi
OFF ON ON Min
OFF
ON
C
Signal OFF Delay
Hi-Lo
ON
ON
ON
hr, min, sec
ON ON
R
Signal
ON
Hi-Hi
Table 1
11.
Terminal Definition
Input connections
CTA4 series
Multi-function input pin
Counter
Timer
Tachometer
Timer + Counter
CP1 CP1
CP1
CP2 Gate Gate
Reset1 Reset1 Reset1 Reset1
Reset2 Start
Start
12.
Dimension & Panel Cutout
CTA4 series
13.
How to Mount
Step-1. Insert the controller through the panel cutout.
Step-2. Insert the mounting bracket into the mounting groove at the top and bottom of the controller and
push the mounting bracket forward until the bracket stops at panel wall.
Step-3. Insert and tighten screws on bracket to secure the controller in place.
Delta Electronics, Inc. 31-1 Shien Pan Road, Kuei Shan Industrial Park, Taoyuan Shien 33341, Taiwan, R.O.C.
TEL: +886-3-362-6301
FAX: +886-3-362-7267
Table 2
The content of this /instruction sheet may be revised without prior notice. Please consult our distributors or
download the most updated version at http://www.delta.com.tw/industrialautomation