Iv. electrical connections – Bryant 905D User Manual
Page 2
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Table I—Ratings and Performance
MODEL
905D
Electrical
Voltage-Freq-Phase
115-60-1
Performance & Physical Data
Evaporative Rate*
5.2 Ibs/hr
Plenum Cutout Dimensions
10-7/8
X
12
Water Supply Line
1/4-in. tube
Overflow Drain Connection
1/2-in.
*Rated in accordance with A.R.I. Standard 610-70.
IV. ELECTRICAL CONNECTIONS
Make all electrical connections in accordance with
National Electric Code and any local codes or or
dinances that may apply.
If aluminum conductors are used, the wire size selec
ted must have a current carrying capacity not less
than that of the copper wire specified and must not
create a voltage drop between the service panel and
the unit in excess of
2
%
of the unit rated voltage. As a
minimum, aluminum wire must be treated to prevent
oxidation, with electric power turned off. Recheck all
electrical connections (both factory and field) for
tightness. Be sure to check power supply connections,
especially if aluminum conductors are used.
Wire the service cord furnished in the parts bag in
parallel with the heating unit fan motor as shown in
the appropriate diagram. See Figures 4, 5, 6, or 7.
-2-